ELE13-03503
| Conference | 12/26/2013 | 12/27/2013 | 12/27/2013 1:19:37 PM | P | CANC |
|
|
Phone #: 2088661213 >> Inspection requested via mobile web by Todd Nelson
|
ELE13-03503
| Electrical Rough-In | 12/27/2013 | 12/27/2013 | 12/27/2013 1:19:03 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested rough-in ok cover
|
ELE13-03181
| Final | 12/27/2013 | 12/27/2013 | 12/27/2013 1:01:49 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender final ok
|
ELE13-03435
| Electrical Rough-In | 12/27/2013 | 12/27/2013 | 12/27/2013 12:38:01 PM | P | PASS |
|
|
Steve Phone #: ###-#### corrections done, rough-in ok cover
|
ELE13-02430
| Electrical Rough-In | 12/27/2013 | 12/27/2013 | 12/27/2013 12:14:54 PM | P | FAIL |
|
|
Grid inspection. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery NEC 314.28 (A)(1) Straight pull, the length of the box shall not be less eight times of the largest raceway, plus sum of diameter of all other entries. Support cabling off ceiling grid
|
ELE13-03473
| Permanent Service | 12/26/2013 | 12/27/2013 | 12/27/2013 9:06:31 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Berthelot p/s u/g rec ok
|
ELE12-01390
| Final | 12/27/2013 | 12/27/2013 | 12/27/2013 8:57:30 AM | A | PASS |
|
|
Listed signs final ok
|
ELE13-03181
| Final | 12/26/2013 | 12/27/2013 | 12/27/2013 8:51:57 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender NEC 210.08 (B) (5) Receptacles within 6 ft. of the outside edge of sink or basin require GFCI protection
|
ELE13-03525
| Permanent Service | 12/26/2013 | 12/27/2013 | 12/27/2013 8:23:28 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Thomas wilson p/s o/h n ok
|