Inspections for the day of: Tuesday, December 27, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02406 Final12/27/201612/27/201612/27/2016 11:38:08 AMPPASS
both signs installed...labelling/disconnect ok...ok to final
ELE12-01841 ELE-Aging Inspection12/27/201612/27/201612/27/2016 10:45:24 AM DONE
still under construction...building space unoccupied...walls built for division of space
ELE16-01961 Electrical Rough-In12/23/201612/27/201612/27/2016 10:20:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton....

captains office, commanders barrics walls and bath hard lids....west wall captains officeunderground stub ups...ok to cover
ELE16-02490 Permanent Service12/23/201612/27/201612/27/2016 9:06:38 AMPPASS
Joe Phone #: ###-####...

p/s u/g n ok
ELE16-02490 Electrical Rough-In12/27/201612/27/201612/27/2016 9:06:13 AMAPASS
Joe Phone #: ###-####...
rough in ok to cover
ELE16-03084 Final12/26/201612/27/201612/27/2016 8:47:21 AMAFAIL
Door code 0152 Phone #: ###-#### Inspection requested via web by TOM BICANDI

1) available fault current label on service needed

2) intersystem bond needs added at service

3) light not installed in mop/water heater closet

4) front office light switch in upside down

5) outlet under bath sink has no power

6) hall switch below thermostat does not operate anything...no electrical plans on site for verification