FIR16-00711
| INSP-Final Inspection | 12/27/2016 | 12/27/2016 | 12/27/2016 1:51:54 PM | P | CANC |
|
|
To be rescheduled for tomorrow morning.
|
BLD16-04254
| FIRE-Final Inspection | 12/26/2016 | 12/27/2016 | 12/27/2016 12:10:58 PM | A | FAIL |
|
|
I spoke to the contractor and to the new owner about this project. I let both know that it is not ready for a final or a temporary at this point in time. The fire sprinkler permit has not been issued and work performed, missing fire extinguishers, missing exit sign/emergency lights, missing ceiling tile (heat trap), testing of the existing exit signs/emergency lights, missing doors and hardware, need verification of annual inspections of the fire sprinkler and fire alarm systems, small documents missing. I let both gentlemen know that for a temporary occupancy an agreement would need to be approved by both the building code and fire code officials. This same information, for a temporary, had been previously emailed to Treasure Valley Fire Protection last week.
We are looking to get a temporary occupancy signature. The owner of the building that will be occupying this space once the minor TI is complete has to be out of his current leased space by December 31st 2016 and needs to move into this new space. Please let me know if you have any questions. The lock box to gain access is located on the south side of the building. The code is 1027. Phone #: ###-#### Inspection requested via web by Drew Moorhouse
|
FIR16-00773
| INSP-Final Inspection | 12/22/2016 | 12/27/2016 | 12/27/2016 11:19:16 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00251
| INSP-Final Inspection | 12/22/2016 | 12/27/2016 | 12/27/2016 10:35:00 AM | A | FAIL |
|
|
Need the knox box, need weather proof devices in the shower areas and Crane Alarm needs to be present to test the AES system that they have an open permit for.
|
BLD16-03508
| FIRE-Final Inspection | 12/22/2016 | 12/27/2016 | 12/27/2016 10:34:00 AM | A | FAIL |
|
|
Inspection turned into a conference in which we discussed the door hardware issues and where to place the exit signs and emergency lights. We discussed fire extinguisher placement and the non-functional fire alarm system that does not meet current code but may have met the code it was installed under. The issue is the approved plans indicate two new strobes and the building only has old bells on the interior walls.
|