Inspections for the day of: Tuesday, December 28, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-04065 Rough-In Permanent Service12/27/200412/28/200412/28/2004 12:00:00 AMAFAIL
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted called 110.26(F)(1) clearence for sub panels move panel or plumbing 12/28/2004 10:08:28 AM
ELE04-04066 Rough-In Permanent Service12/27/200412/28/200412/28/2004 12:00:00 AMAFAIL
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted called 110.26(F)(2) move sub panels or plumbing 12/28/2004 10:09:19 AM
ELE04-04068 Rough-In Permanent Service12/27/200412/28/200412/28/2004 12:00:00 AMAPASS
Darrell; Phone #: ###-#### Internet Inspection Request from: Jan Rice r/i ok
p/s o/h new ok 12/28/2004 9:05:04 AM
ELE04-01830 Rough-In Permanent Service12/27/200412/28/200412/28/2004 12:00:00 AMAFAIL
please call for access mike ###-#### cor. posted met contractor 250.52(A)(1) grd to water, 110.26(F)(2) clearence for service,,250.8 no SMS, shall not ID 6 or smaller grds and neutrals , bond bushing for RE washers, use manufactures equip grd bus, job not ready 12/28/2004 9:19:37 AM
ELE04-03657 Rough-In Permanent Service12/27/200412/28/200412/28/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/27/2004 at 10:09:46 AM. Contact: ###-####. r/i 4 units ok
p/s u/g new ok 12/28/2004 3:17:01 PM
ELE04-03705 Final12/28/200412/28/200412/28/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn ok 12/28/2004 12:19:10 PM
ELE03-03652 Final12/28/200412/28/200412/28/2004 12:00:00 AMPNR
Nick; Phone #: ###-#### Internet Inspection Request from: Jan Rice see added r/i 12/28/2004 1:53:13 PM
ELE04-04074 Rough-In Permanent Service12/28/200412/28/200412/28/2004 12:00:00 AMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted called550.32(B) (1thur7) follow code noted if service is on trailer, 230.28 guy kit for mast, re bar of concrete encased electrode shall be encased in concrete to above grade if ? call jack
12/28/2004 1:01:56 PM
ELE04-03557 Electrical Rough-In12/28/200412/28/200412/28/2004 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 12/28/2004 at 11:11:23 AM. Contact: ###-####. contractor called 12/28/2004 11:48:29 AM
ELE03-03652 Electrical Rough-In12/28/200412/28/200412/28/2004 12:00:00 AMPPASS
r/i ok
ELE04-01475 Final12/28/200412/28/200412/28/2004 12:00:00 AMPPART
called left message