ELE05-04622
| Final | 12/27/2005 | 12/28/2005 | 12/29/2005 12:04:49 AM | P | FAIL |
|
|
inspection for hot tub. Outside in back yard, enter thru east gate, no dogs in yard. Home owner is Bob Mortensen.; Phone #: ###-#### Internet Inspection Request from: todd hall 1. 110.2/110.3 listing/labeling 2. 680.22A3 recep 10'-20' 3. 680.22A5 gfci recep protection 4. 680.26B4 bonding of internal equipment 5. 406.8B1 in use cover required
|
ELE05-04188
| Final | 12/28/2005 | 12/28/2005 | 12/28/2005 4:35:37 PM | P | PASS |
|
|
Request Inspector Pat Lass to call Wayne @ ###-#### to get a key to the property. Sorry we missed you this A.M.; Phone #: ###-#### Internet Inspection Request from: Barry Kendall
|
ELE05-04411
| Electrical Rough-In | 12/28/2005 | 12/28/2005 | 12/28/2005 4:35:17 PM | P | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa RI OK
|
ELE05-04627
| Rough-In Permanent Service | 12/28/2005 | 12/28/2005 | 12/28/2005 2:58:40 PM | P | FAIL |
|
|
Larry ###-####//open access B.C.C.- CONCRETE ENCASED ELCETRODE 300.4- NAIL PLATES EVERYWHERE 210.52- RECEP WITHIN 3' OF SINK AND NEEDS TO BE 20AMP
|
ELE04-01703
| Final | 12/28/2005 | 12/28/2005 | 12/28/2005 2:20:55 PM | P | PASS |
|
|