Inspections for the day of: Thursday, December 28, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03638 ELE-Aging Inspection12/28/200612/28/200612/29/2006 7:25:09 AM CANC
ELE06-04608 Final12/28/200612/28/200612/28/2006 3:24:53 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Tollie Rogers corr fee due posted called,110.12(A) seal all KOs, 314.25 install covers all boxes, 400.8 shall not use cords for fixed wiring shall not be above ceilings and shall remove recept from above ceiling, correction posted to bld06-03430 for all low voltage remove all abandonded cables shall support all cables, cables shall not lay on grid
ELE06-02957 Permanent Service12/27/200612/28/200612/28/2006 2:16:12 PMPPASS
Don; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
p/s u/g new ok
ELE06-02957 Rough-In Permanent Service12/27/200612/28/200612/28/2006 2:15:41 PMPPASS
donnie - ceiling cover ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith r/i ceiling ok p/s u/g new ok
ELE06-03766 Rough-In Permanent Service12/28/200612/28/200612/28/2006 12:20:50 PMPPASS
dino ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
p/s u/g new ok
ELE06-04001 Final12/27/200612/28/200612/28/2006 10:57:52 AMAPASS
DENNIS; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok no card
ELE06-04038 Electrical Rough-In12/27/200612/28/200612/28/2006 10:57:28 AMAPART
DENNIS; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
soffit lights
ELE06-03691 Final12/27/200612/28/200612/28/2006 10:06:30 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok called survey 410.8 clearence for closet fixtures in bed rm closets non master
ELE06-04673 Electrical Rough-In12/27/200612/28/200612/28/2006 9:29:50 AMAPART
Partial rough in inspection for kitchen only Internet Inspection Request from: Phil Baker
ok
ELE06-04306 Final12/27/200612/28/200612/28/2006 8:33:56 AMAFAIL
Re-inspection; Phone #: ###-#### Internet Inspection Request from: Barry Kendall corr. not made called needs gfci protection for recept