Inspections for the day of: Thursday, December 28, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01919 Final12/27/200612/28/200612/28/2006 4:10:46 PMPFAIL
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not done, needs to install afci and strap gounding electrode conductor to house, rest ok
ELE06-02073 Electrical Rough-In12/28/200612/28/200612/28/2006 3:31:51 PMPNR
brian - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner we need to see outside recpt and light for ri
ELE06-04710 Rough-In Permanent Service12/28/200612/28/200612/28/2006 2:14:29 PMPCANC
Scheduled by a contractor via Hello! on 12/28/2006 at 10:09:13 AM. Contact: ###-####. see ri and p/s
ELE06-04710 Electrical Rough-In12/28/200612/28/200612/28/2006 2:14:00 PMPFAIL
Scheduled by a contractor via Hello! on 12/28/2006 at 10:09:13 AM. Contact: ###-####. called left corr notice, nec 210.70(A)(3) equip space shall have switched lighting outlet, 210.63 recpt shall be installed in equip room , 300.14 6" of free conductor shall be provided at fan box,BCC all make-up shall be done, boxes installed, will see u/g to garage ltr, service panel may lose work space unless a/c lines are moved
ELE06-04710 Permanent Service12/28/200612/28/200612/28/2006 2:06:45 PMPPASS
Scheduled by a contractor via Hello! on 12/28/2006 at 10:09:13 AM. Contact: ###-####. p/s u/g n ok
ELE06-02454 Electrical Rough-In12/28/200612/28/200612/28/2006 1:33:59 PMPNR
charlene;cell ####-#### Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner to make-up grounds and let us see before we give ok to cover
ELE06-04711 Temporary Service12/28/200612/28/200612/28/2006 1:11:58 PMPFAIL
brandon ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection, BCC address shall be posted
ELE06-04230 Electrical Rough-In12/27/200612/28/200612/28/2006 10:51:27 AMAPASS
in-floor heating, under tile. Tile guy should be there for access. To ensure access pls call contractor - Tim Gammill 1/2 hr before @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to cover floor for heat
ELE06-04689 Temporary Service12/27/200612/28/200612/28/2006 10:49:30 AMAPASS
Kelly Tarter ###-#### Temp power service inspection; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson t/s u/g n ok, called left message
ELE06-04710 Electrical Rough-In12/27/200612/28/200612/28/2006 9:39:15 AMANH
Zane; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, told contr to call in what wants and when not locked up
ELE06-04705 Electrical Rough-In12/27/200612/28/200612/28/2006 9:05:16 AMANH
Work performed by Steve Johnson. Talk to Dustin ###-####; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called, left message, told to call when people availabe
ELE06-04253 Final12/27/200612/28/200612/28/2006 8:45:41 AMAPASS
Phone #: ###-#### x1379 Internet Inspection Request from: Daryl DeGrange ok to final
ELE06-04709 Final12/27/200612/28/200612/28/2006 8:45:11 AMANH
Work performed by Ron Chaney.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz white pine school, called contr, will reschedule when people available
ELE06-04209 Final12/27/200612/28/200612/28/2006 8:07:37 AMAPASS
Phone #: ###-#### x007 Internet Inspection Request from: Daryl DeGrange ok to final