Inspections for the day of: Thursday, December 28, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00585 FIR-Aging Inspection12/28/200612/28/20061/3/2007 3:58:31 PM NR
work is in progress
FIR06-00710 INSP-Final Inspection12/27/200612/28/200612/29/2006 4:00:18 PMAPART
A temporary occupancy was given with dave hannimans permission until the sprinkler design/aisle widths are figured out.
FIR06-00491 INSP-Final Inspection12/28/200612/28/200612/28/2006 5:04:08 PMPFAIL
Need as-builts showing the deleted duct detector and revised zones, provide revized map at the facp and provide the NFPA 72 forms.
BLD06-02211 FIRE-Final Inspection12/27/200612/28/200612/28/2006 5:02:01 PMAFAIL
Lower and tag fire extinguishers. Provide correct sample tubes and remote annunciators for the duct smoke detectors.
BLD06-02883 FIRE-Final Inspection12/27/200612/28/200612/28/2006 1:56:56 PMPPASS
Life safety finaled
FIR06-00710 INSP-Sprinkler Rough-in/Hydro12/27/200612/28/200612/28/2006 1:54:04 PMAFAIL
The rack system overhead hydro test failed. All other items have been corrected. Forward flush passed.
FIR06-00878 INSP-Final Inspection12/27/200612/28/200612/28/2006 12:50:10 PMPPASS
permit finaled
FIR06-00853 INSP-Supply line flush12/27/200612/28/200612/28/2006 11:40:22 AMAPASS
Forward flush passed.1,180 gallons was verified through a diffuser and a play pipe. Need lid for the vault for final.
FIR06-00738 INSP-Final Inspection12/27/200612/28/200612/28/2006 10:18:24 AMAPASS
permit finaled
FIR06-01004 INSP-Final Inspection12/27/200612/28/200612/28/2006 9:06:52 AMAPASS
permit finaled