Inspections for the day of: Friday, December 28, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02451 Electrical Rough-In12/26/200712/28/200712/28/2007 2:57:15 PMPPART
Rough In approve for cover interior walls. Please call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok anop
ELE07-04133 Permanent Service12/28/200712/28/200712/28/2007 2:09:55 PMPPASS
jeff Phone #: ###-#### needs #4 to water
p/s o/h rec. ok
ELE07-04225 Permanent Service12/28/200712/28/200712/28/2007 1:25:40 PMPNR
dan Phone #: ###-#### needs to change or protect #8 GEC, 250.52(A !), 104(A!) shall grd within 5ft or bond water, T 220.55 shall install required size circuit for range , 314.3 needs bond bushings for metallic raceways in plastic jbox
ELE07-03088 Final12/27/200712/28/200712/28/2007 12:51:16 PMPFAIL
BUSTER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
needs panel set and meter installed , no power to building met contr
ELE07-03048 Final12/27/200712/28/200712/28/2007 12:50:33 PMPFAIL
BUSTER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
needs panel set and meter installed for final, met contr, no power to building
ELE07-02894 Final12/28/200712/28/200712/28/2007 10:43:53 AMAFAIL
Scheduled by a contractor via Hello! on 12/28/2007 at 7:25:53 AM. Contact: ###-####. corr called 110.3(B) needs manufactures instruction and required size access for jtub, 408.4 be specific panel schedule
ELE07-04040 Final12/27/200712/28/200712/28/2007 9:50:33 AMAFAIL
REQUEST THAT JACK FRANK BE THE INSPECTOR. PLEASE PHONE RYAN @ ###-#### OR SETH @ ###-#### 1 HOUR IN ADVANCE SO ONE OF THEM CAN MEET YOU THERE... PLEASE SCHEDULE FOR A LATE AM INSPECTION. THANK YOU! Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see notes to added fee due
ELE07-03217 Final12/27/200712/28/200712/28/2007 8:59:08 AMAPART
Please inspect all machine wiring. Please call Dustin before going. ###-####. Thanks! Phone #: ###-#### Internet Inspection Request from: Monica Cortez
needs to replace cord used as fixed wiring
ELE07-03712 Electrical Rough-In12/27/200712/28/200712/28/2007 8:22:08 AMAFAIL
jessie - note: ceiling Phone #: ###-####
not ready and shall not use under size wire to exit lights they are not whips by nec definition