ELE07-02451
| Electrical Rough-In | 12/26/2007 | 12/28/2007 | 12/28/2007 2:57:15 PM | P | PART |
|
|
Rough In approve for cover interior walls. Please call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok anop
|
ELE07-04133
| Permanent Service | 12/28/2007 | 12/28/2007 | 12/28/2007 2:09:55 PM | P | PASS |
|
|
jeff Phone #: ###-#### needs #4 to water p/s o/h rec. ok
|
ELE07-04225
| Permanent Service | 12/28/2007 | 12/28/2007 | 12/28/2007 1:25:40 PM | P | NR |
|
|
dan Phone #: ###-#### needs to change or protect #8 GEC, 250.52(A !), 104(A!) shall grd within 5ft or bond water, T 220.55 shall install required size circuit for range , 314.3 needs bond bushings for metallic raceways in plastic jbox
|
ELE07-03088
| Final | 12/27/2007 | 12/28/2007 | 12/28/2007 12:51:16 PM | P | FAIL |
|
|
BUSTER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy needs panel set and meter installed , no power to building met contr
|
ELE07-03048
| Final | 12/27/2007 | 12/28/2007 | 12/28/2007 12:50:33 PM | P | FAIL |
|
|
BUSTER Phone #: ###-#### Internet Inspection Request from: Sean DeLacy needs panel set and meter installed for final, met contr, no power to building
|
ELE07-02894
| Final | 12/28/2007 | 12/28/2007 | 12/28/2007 10:43:53 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/28/2007 at 7:25:53 AM. Contact: ###-####. corr called 110.3(B) needs manufactures instruction and required size access for jtub, 408.4 be specific panel schedule
|
ELE07-04040
| Final | 12/27/2007 | 12/28/2007 | 12/28/2007 9:50:33 AM | A | FAIL |
|
|
REQUEST THAT JACK FRANK BE THE INSPECTOR. PLEASE PHONE RYAN @ ###-#### OR SETH @ ###-#### 1 HOUR IN ADVANCE SO ONE OF THEM CAN MEET YOU THERE... PLEASE SCHEDULE FOR A LATE AM INSPECTION. THANK YOU! Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see notes to added fee due
|
ELE07-03217
| Final | 12/27/2007 | 12/28/2007 | 12/28/2007 8:59:08 AM | A | PART |
|
|
Please inspect all machine wiring. Please call Dustin before going. ###-####. Thanks! Phone #: ###-#### Internet Inspection Request from: Monica Cortez needs to replace cord used as fixed wiring
|
ELE07-03712
| Electrical Rough-In | 12/27/2007 | 12/28/2007 | 12/28/2007 8:22:08 AM | A | FAIL |
|
|
jessie - note: ceiling Phone #: ###-#### not ready and shall not use under size wire to exit lights they are not whips by nec definition
|