Inspections for the day of: Friday, December 28, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00558 Final12/28/200712/28/200712/28/2007 3:41:02 PMPFAIL
eric Phone #: ###-#### met owner, left correction notice, nec 210.12(B) bedrooms shall have afci protection installed, 406.8(A) garage outdoor recptacle shall have in-use cover installed, asked owner to strap conduit that was existing in garage, everything else in house inspected, told could move in, but we have to inspect afci and owner must provide room for access
ELE07-03879 Rough-In Permanent Service12/28/200712/28/200712/28/2007 2:36:37 PMPFAIL
jeremey ###-#### called, left message, left corr notice,nec 404.8 center grip of breaker handle at service shall not be over 6'-7" above grade, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box, 408.7 unused breaker openings shall be closed, BCC all make-up shall be done including boxes- out back, kitchen, and boxes shall have wiring installed, no u/g to garage seen or done, disconnects for garage service not done
ELE06-03143 Electrical Rough-In12/28/200712/28/200712/28/2007 1:36:22 PMPPART
ed Phone #: ###-#### ok to cover ceiling 3rd floor south side anop
ELE07-04144 Final12/27/200712/28/200712/28/2007 12:54:54 PMPPASS
PAUL CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked with contractor, saw cleaned up installation, ok to final
ELE07-04212 Permanent Service12/27/200712/28/200712/28/2007 10:38:05 AMACANC
james Phone #: ###-#### gave ok yesterday, see final
ELE07-04212 Final12/28/200712/28/200712/28/2007 10:00:38 AMAPASS
james Phone #: ###-#### called contractor to finish circuit schedule, ok to final
ELE07-03785 Final12/27/200712/28/200712/28/2007 9:55:54 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to final, signed occupancy card
ELE07-03478 Electrical Rough-In12/27/200712/28/200712/28/2007 9:25:34 AMAPASS
RI - for questions pls call Randy w/ Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to cover dressing room walls anop
ELE07-04135 Electrical Rough-In12/27/200712/28/200712/28/2007 9:20:39 AMAPASS
Joe Phone #: ###-#### ok to cover conference room walls
ELE07-04217 Final12/27/200712/28/200712/28/2007 7:53:22 AMACANC
Call Randy''s cell at ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
ELE07-03712 Electrical Rough-In12/28/200712/28/200712/28/2007 12:00:00 AMPCANC
jesse Phone #: ###-####