Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02899 Extend Permit 180 days12/21/200712/21/2007 P 
FIR07-00759 INSP-Final Inspection12/28/200712/28/200712/28/2007 4:39:39 PMPFAIL
Relocate SD at classroom #1 too close to HVAC diffuser, relocate one manual pull station at the SW exit door from the sanctuary that is too high, add notification devices at the faculty lounge and room 128 in use as an "art room", need to demo the old FACP, provide covers at two open junction boxes classroom #3, provide signage at the door to the FACP, post a current map at the panel including correct FACP, smoke and nac panel locations, see fire code review notes items #24 and #5 for knox box requirement and HVAC information regarding possible duct smoke detection required.
BLD07-01673 FIRE-Final Inspection12/27/200712/28/200712/28/2007 4:31:28 PMPPASS
Fire life safety inspection passed, keyed locking hardware at two office doors removed while on site.
BLD07-02356 FIRE-Final Inspection12/27/200712/28/200712/28/2007 2:17:36 PMAPASS
Fire life safety inspection passed, noted manual flush bolts at the inactive door leaf from the conference room must be removed or provide automatic style prior to structural final.
FIR07-00884 INSP-Final Inspection12/27/200712/28/200712/28/2007 2:15:41 PMAPASS
Fire sprinkler permit work finaled.
FIR07-00943 INSP-Final Inspection12/27/200712/28/200712/28/2007 2:13:45 PMAPASS
C/N verified for compliance, fire alarm permit finaled.
FIR07-00885 INSP-Sprinkler Rough-in12/27/200712/28/200712/28/2007 10:02:54 AMAPART
Required corrections from the previous visit are complete, overhead install is approved for cover at both the drop and hard lid ceilings.