Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00754 INSP-Sprinkler Rough-in/Hydro12/22/200912/28/200912/28/2009 4:51:02 PMPDEFR
Intended for alarm final
FIR09-00622 INSP-Final Inspection12/24/200912/28/200912/28/2009 4:28:50 PMAPART
Completed testing for duct detectors at areas A , F and mezzanines, retest DD at area D tool crib and area B office passed, incorrect sample tube orientation at AHU 28 fixed while on site, manual pull stations throughout tested okay, tamper switches at the sprinkler riser okayed, need to verify correct test orfice sizes at riser manifold prior to flow switch testing, two duct detectors at the Jenny Craig production line lacking access due to floor finishes underway, verified missing a/v has been installed at area D warehouse, relay for mag locks at the main entry is not ready for testing per contractor.
BLD09-01427 FIRE-Final Inspection12/24/200912/28/200912/28/2009 4:09:34 PMAPASS
Fire life safety finaled.
BLD08-02600 FIRE-Final Inspection12/28/200912/28/200912/28/2009 3:54:41 PMAPASS
Fire life safety inspection passed, correction notice items completed.
FIR09-00364 INSP-Final Inspection12/28/200912/28/200912/28/2009 3:53:40 PMAPASS
Fire sprinkler permit work passed final inspection.