FIR10-00578
| INSP-Final Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 2:35:39 PM | P | PASS |
|
|
Permit finaled.
|
FIR10-00578
| INSP-Alarm Testing | 12/21/2010 | 12/28/2010 | 12/28/2010 2:34:43 PM | P | PASS |
|
|
Correction items verified for completion. Hood suppression system operated correctly under test conditions.
|
BLD10-00735
| FIRE-Final Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 2:05:15 PM | P | FAIL |
|
|
Duct detector at the north side RTU failed to shut the unit down upon smoke head activation. Correction items per review note items 5 and 7 are satisfactory.
|
FIR10-00425
| INSP-Sprinkler Rough-in | 12/27/2010 | 12/28/2010 | 12/28/2010 1:33:20 PM | A | PART |
|
|
Overhead rough-in approved for cover at the office area grid ceilings. Need to provide coverage below the 6'x6' hood at the shop bay, include seismic clearance at main penetrations through non-frangible wall construction, install correct temp. rated heads within the zone of influence at unit heaters in the shop areas (SW and uprights).
|
FIR08-00155
| FIR-Aging Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 1:26:10 PM | | FAIL |
|
|
See permit activity notes.
|
FIR08-00764
| FIR-Aging Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 1:24:21 PM | | FAIL |
|
|
No call for inspection.
|
FIR08-00239
| FIR-Aging Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 1:21:49 PM | | DONE |
|
|
Construction suspended.
|
FIR08-00119
| FIR-Aging Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 1:21:04 PM | | DONE |
|
|
Ref. activity notes 11/18.
|