FIR10-00578 INSP-Final Inspection12/28/201012/28/201012/28/2010 2:35:39 PMPPASS
Permit finaled.
FIR10-00578 INSP-Alarm Testing12/21/201012/28/201012/28/2010 2:34:43 PMPPASS
Correction items verified for completion. Hood suppression system operated correctly under test conditions.
BLD10-00735 FIRE-Final Inspection12/28/201012/28/201012/28/2010 2:05:15 PMPFAIL
Duct detector at the north side RTU failed to shut the unit down upon smoke head activation. Correction items per review note items 5 and 7 are satisfactory.
FIR10-00425 INSP-Sprinkler Rough-in12/27/201012/28/201012/28/2010 1:33:20 PMAPART
Overhead rough-in approved for cover at the office area grid ceilings. Need to provide coverage below the 6'x6' hood at the shop bay, include seismic clearance at main penetrations through non-frangible wall construction, install correct temp. rated heads within the zone of influence at unit heaters in the shop areas (SW and uprights).
FIR08-00155 FIR-Aging Inspection12/28/201012/28/201012/28/2010 1:26:10 PM FAIL
See permit activity notes.
FIR08-00764 FIR-Aging Inspection12/28/201012/28/201012/28/2010 1:24:21 PM FAIL
No call for inspection.
FIR08-00239 FIR-Aging Inspection12/28/201012/28/201012/28/2010 1:21:49 PM DONE
Construction suspended.
FIR08-00119 FIR-Aging Inspection12/28/201012/28/201012/28/2010 1:21:04 PM DONE
Ref. activity notes 11/18.