FIR12-00267
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 3:37:34 PM | P | CANC |
|
|
To be rescheduled per mike and I's conversation.
|
BLD05-01282
| FIRE-Final Inspection | 12/27/2012 | 12/28/2012 | 12/28/2012 3:17:25 PM | P | FAIL |
|
|
The existing fire alarm system needs to be extended into the new area as per review comment #17.
|
FIR12-00328
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 3:07:34 PM | P | FAIL |
|
|
Will be able to final when the call list has been set up and the NFPA 72 are complete.
|
FIR12-00327
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 3:06:47 PM | P | FAIL |
|
|
Will be able to final when the call list has been set up and the NFPA 72 are complete.
|
BLD12-01461
| FIRE-Final Inspection | 12/27/2012 | 12/28/2012 | 12/28/2012 2:19:26 PM | P | FAIL |
|
|
Will be ok to final when the project related fire alarm permit is finaled
|
FIR12-00640
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 2:15:40 PM | P | FAIL |
|
|
The music did not shut down/reduce as required. THis is the last remaining item prior to a final sign offf.
|
FIR12-00483
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 2:10:11 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00666
| INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 2:08:09 PM | P | FAIL |
|
|
Project is not ready for inspection. The system had not been turned on or pre-tested prior to inspection. I performed a walk around and noted on the city approved plans located where strobes are over spaced, have been added or deleted. It appears that strobes to the east of column line 8 will be blocked by racking that exceeds 6' in height. We did set off the audio/visuals after activating the panel and I found that neither the audio or visuals are sync'd. Per the fire alarm plans examiner due to small safety factor for the EOL voltages any changes will require a plan modification. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
|
BLD12-02323
| FIRE-Final Inspection | 12/27/2012 | 12/28/2012 | 12/28/2012 2:01:53 PM | A | FAIL |
|
|
Life safety is ok to final when the project related fire alarm permit is passed. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
|
BLD12-03314
| FIRE-Final Inspection | 12/27/2012 | 12/28/2012 | 12/28/2012 11:49:58 AM | A | FAIL |
|
|
Provide annual inspection for the fire sprinkler system, provide verification the existing fire alarm system is monitored, repair the exit signs and emergency lights, provide fire extinguishers as discussed. I also discussed racking permit requirements with the applicant.
|
FIR12-00614
| INSP-Final Inspection | 12/27/2012 | 12/28/2012 | 12/28/2012 11:47:47 AM | A | PASS |
|
|
Permit finaled
|