Inspections for the day of: Friday, December 28, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00267 INSP-Final Inspection12/28/201212/28/201212/28/2012 3:37:34 PMPCANC
To be rescheduled per mike and I's conversation.
BLD05-01282 FIRE-Final Inspection12/27/201212/28/201212/28/2012 3:17:25 PMPFAIL
The existing fire alarm system needs to be extended into the new area as per review comment #17.
FIR12-00328 INSP-Final Inspection12/28/201212/28/201212/28/2012 3:07:34 PMPFAIL
Will be able to final when the call list has been set up and the NFPA 72 are complete.
FIR12-00327 INSP-Final Inspection12/28/201212/28/201212/28/2012 3:06:47 PMPFAIL
Will be able to final when the call list has been set up and the NFPA 72 are complete.
BLD12-01461 FIRE-Final Inspection12/27/201212/28/201212/28/2012 2:19:26 PMPFAIL
Will be ok to final when the project related fire alarm permit is finaled
FIR12-00640 INSP-Final Inspection12/28/201212/28/201212/28/2012 2:15:40 PMPFAIL
The music did not shut down/reduce as required. THis is the last remaining item prior to a final sign offf.
FIR12-00483 INSP-Final Inspection12/28/201212/28/201212/28/2012 2:10:11 PMPPASS
Permit finaled
FIR12-00666 INSP-Final Inspection12/28/201212/28/201212/28/2012 2:08:09 PMPFAIL
Project is not ready for inspection. The system had not been turned on or pre-tested prior to inspection. I performed a walk around and noted on the city approved plans located where strobes are over spaced, have been added or deleted. It appears that strobes to the east of column line 8 will be blocked by racking that exceeds 6' in height. We did set off the audio/visuals after activating the panel and I found that neither the audio or visuals are sync'd. Per the fire alarm plans examiner due to small safety factor for the EOL voltages any changes will require a plan modification. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
BLD12-02323 FIRE-Final Inspection12/27/201212/28/201212/28/2012 2:01:53 PMAFAIL
Life safety is ok to final when the project related fire alarm permit is passed. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
BLD12-03314 FIRE-Final Inspection12/27/201212/28/201212/28/2012 11:49:58 AMAFAIL
Provide annual inspection for the fire sprinkler system, provide verification the existing fire alarm system is monitored, repair the exit signs and emergency lights, provide fire extinguishers as discussed. I also discussed racking permit requirements with the applicant.
FIR12-00614 INSP-Final Inspection12/27/201212/28/201212/28/2012 11:47:47 AMAPASS
Permit finaled