Inspections for the day of: Monday, December 28, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-04097 Permanent Service12/28/201512/28/201512/28/2015 3:33:32 PMPPASS
new ground rods are located on the back left side of garage. Phone #: ###-#### Inspection requested via web by Jason Wicks p/s o/h rec ok
ELE15-03906 Electrical Rough-In12/24/201512/28/201512/28/2015 3:08:02 PMPPASS
Phone #: ###-#### Inspection requested via web by Jonathan Poot r/i ok upst. and dnst. Will install nailplates and staples as per our conversation
ELE15-02615 Final12/28/201512/28/201512/28/2015 2:08:11 PMPFAIL
Phone #: ###-#### Inspection requested via web by Zane Robertson equipment listed, floor boxes fed with proper wiring. BUT 517.18(B)- all receptacles in procedure rooms shall be listed "hospital grade" and shall be so identified. 110.16-Arc flash warning label required on loadcenters. Update panel schedule
ELE15-04089 Conference12/24/201512/28/201512/28/2015 11:34:04 AMADONE
Underground conference, please contact Craig Timmons Phone #: ###-#### Inspection requested via web by Cathy Duchek discuss ufer terminaion point Bring grounding electrode conductor to electric room. Bond neutrals at each main disconnect. Bring fire pump feed straight to fire pump room. Bond nuetral in termination cabinet to can
ELE15-04090 Final12/24/201512/28/201512/28/2015 9:06:42 AMAFAIL
Someone will be there. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 12-2 nm cable for peninsular receptacle laying under floor , C/U says 25 amp max., garage not done, we can give partial final on house for now when ready.
ELE15-03395 Final12/24/201512/28/201512/28/2015 8:29:24 AMAPASS
Heated floor - Warren Phone #: ###-#### final ok
ELE15-04076 Final12/28/201512/28/201512/28/2015 8:06:25 AMAPASS
final on led exterior Phone #: ###-#### Inspection requested via web by Tim Dunlop final ok pole light retro