Inspections for the day of: Wednesday, December 28, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00766 INSP-Sprinkler Rough-in12/28/201612/28/201612/28/2016 1:05:19 PMPPASS
Rough-in passed. Piping can be covered.
BLD16-04435 FIRE-Final Inspection12/28/201612/28/201612/28/2016 11:57:34 AMPPASS
Life safety passed. I went over storage height restrictions with the owner.
BLD16-03467 FIRE-Final Inspection12/27/201612/28/201612/28/2016 9:49:23 AMAFAIL
Provide clarification for the "access controled egress doors" as discussed and provide a fire alarm permit for the fire alarm system modifications.
FIR16-00711 INSP-Final Inspection12/27/201612/28/201612/28/2016 8:33:26 AMAFAIL
The new strobes are mounted too low. Installer apparently matched existing heights. I need the new devices to be installed at the correct height and the existing strobes in the remodel area/path of egress to meet current code or provide verification that they met code when they were installed.