Inspections for the day of: Thursday, December 28, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04341 Final12/28/201712/28/201712/28/2017 2:11:25 PMPPASS
Call paul with any questions.Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer...ok to final
ELE17-04306 Permanent Service12/28/201712/28/201712/28/2017 1:25:35 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin...p/s new ok
ELE17-03497 Final12/28/201712/28/201712/28/2017 12:06:26 PMPPASS
Garage Code 5233 Phone #: ###-#### Inspection requested via web by Ben Grundhauser...corrections made...ok to final
ELE17-04320 Temporary Service12/28/201712/28/201712/28/2017 11:40:49 AMPFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn...
1) all openings in panel board shall be sealed..open to busing...missing breaker
2) ground wire shall be sufficient to attach to ground rod
3) attachment to ground rod shall be complete with all strands under acorn to get proper ground
ELE17-04319 Temporary Service12/28/201712/28/201712/28/2017 11:32:37 AMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...t/s u/g new ok
ELE17-04316 Temporary Service12/28/201712/28/201712/28/2017 11:27:13 AMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...t/s u/g new ok
ELE12-02548 Final12/28/201712/28/201712/28/2017 11:03:34 AMAPASS
contact no longer works for contractor...no corrections were needed at time of perm service..contact assures all circuits labelled and job complete...ok to final
ELE12-02548 ELE-Aging Inspection12/28/201712/28/201712/28/2017 11:01:37 AM DONE
see final notes
ELE12-02580 ELE-Aging Inspection12/28/201712/28/201712/28/2017 10:51:06 AM FAIL
have made contact with contractor more than once and still waiting to schedule inspection
ELE17-04337 Rough-In Permanent Service12/28/201712/28/201712/28/2017 10:23:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by Neal Rumsey....
1) service panelboard barriers need installed on all ungrounded conductors..408.3(A)(2)
2) uffer ground connection shall be made accessible..250.68(A)
3) wall space 2' or greater shall have an outlet..210.52(A)(2)...2 places marked
ELE17-04335 Electrical Rough-In12/27/201712/28/201712/28/2017 9:40:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Cyndi Dale.... wall and hardlid ok to cover...6 outlets added in cubical area, new bath south side, new bath north side....northside bath shall have access to junction boxes or they need moved...check at ceiling inspection
ELE17-03746 Final12/27/201712/28/201712/28/2017 9:15:45 AMAPASS
access 0726 Phone #: ###-#### Inspection requested via web by David Nelson...ok to final
ELE17-04309 Rough-In Permanent Service12/27/201712/28/201712/28/2017 8:45:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...rough ok to cover...p/s u/g new ok
ELE13-03180 ELE-Aging Inspection12/28/201712/28/201712/28/2017 8:02:52 AM FAIL
contractor has been made aware of need for final inspection
ELE12-02616 ELE-Aging Inspection12/28/201712/28/201712/28/2017 7:58:47 AM DONE
permit holder works out of state