ELE17-04341
| Final | 12/28/2017 | 12/28/2017 | 12/28/2017 2:11:25 PM | P | PASS |
|
|
Call paul with any questions.Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer...ok to final
|
ELE17-04306
| Permanent Service | 12/28/2017 | 12/28/2017 | 12/28/2017 1:25:35 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin...p/s new ok
|
ELE17-03497
| Final | 12/28/2017 | 12/28/2017 | 12/28/2017 12:06:26 PM | P | PASS |
|
|
Garage Code 5233 Phone #: ###-#### Inspection requested via web by Ben Grundhauser...corrections made...ok to final
|
ELE17-04320
| Temporary Service | 12/28/2017 | 12/28/2017 | 12/28/2017 11:40:49 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1) all openings in panel board shall be sealed..open to busing...missing breaker 2) ground wire shall be sufficient to attach to ground rod 3) attachment to ground rod shall be complete with all strands under acorn to get proper ground
|
ELE17-04319
| Temporary Service | 12/28/2017 | 12/28/2017 | 12/28/2017 11:32:37 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn...t/s u/g new ok
|
ELE17-04316
| Temporary Service | 12/28/2017 | 12/28/2017 | 12/28/2017 11:27:13 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn...t/s u/g new ok
|
ELE12-02548
| Final | 12/28/2017 | 12/28/2017 | 12/28/2017 11:03:34 AM | A | PASS |
|
|
contact no longer works for contractor...no corrections were needed at time of perm service..contact assures all circuits labelled and job complete...ok to final
|
ELE12-02548
| ELE-Aging Inspection | 12/28/2017 | 12/28/2017 | 12/28/2017 11:01:37 AM | | DONE |
|
|
see final notes
|
ELE12-02580
| ELE-Aging Inspection | 12/28/2017 | 12/28/2017 | 12/28/2017 10:51:06 AM | | FAIL |
|
|
have made contact with contractor more than once and still waiting to schedule inspection
|
ELE17-04337
| Rough-In Permanent Service | 12/28/2017 | 12/28/2017 | 12/28/2017 10:23:07 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey.... 1) service panelboard barriers need installed on all ungrounded conductors..408.3(A)(2) 2) uffer ground connection shall be made accessible..250.68(A) 3) wall space 2' or greater shall have an outlet..210.52(A)(2)...2 places marked
|
ELE17-04335
| Electrical Rough-In | 12/27/2017 | 12/28/2017 | 12/28/2017 9:40:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Cyndi Dale.... wall and hardlid ok to cover...6 outlets added in cubical area, new bath south side, new bath north side....northside bath shall have access to junction boxes or they need moved...check at ceiling inspection
|
ELE17-03746
| Final | 12/27/2017 | 12/28/2017 | 12/28/2017 9:15:45 AM | A | PASS |
|
|
access 0726 Phone #: ###-#### Inspection requested via web by David Nelson...ok to final
|
ELE17-04309
| Rough-In Permanent Service | 12/27/2017 | 12/28/2017 | 12/28/2017 8:45:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn...rough ok to cover...p/s u/g new ok
|
ELE13-03180
| ELE-Aging Inspection | 12/28/2017 | 12/28/2017 | 12/28/2017 8:02:52 AM | | FAIL |
|
|
contractor has been made aware of need for final inspection
|
ELE12-02616
| ELE-Aging Inspection | 12/28/2017 | 12/28/2017 | 12/28/2017 7:58:47 AM | | DONE |
|
|
permit holder works out of state
|