MEC18-06069
| Final | 12/27/2018 | 12/28/2018 | 12/28/2018 4:20:37 PM | P | PASS |
|
|
Please call Dave prior to arrival ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil ducting co ok
|
MEC18-06121
| Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 3:41:04 PM | P | FAIL |
|
|
GARAGE CODE 1022 Phone #: ###-#### Inspection requested via web by Oleg Chervak- needs weather tight electrical whip at condenser location- needs secondary drain ran to garage floor with no offset- need to insulate R/A to R-6 in garage- need 3 screws in all flue joints some are missing- recall in when corrections are made
|
MEC18-05903
| Pressure Test | 12/28/2018 | 12/28/2018 | 12/28/2018 2:58:48 PM | P | PASS |
|
|
The inspector has already been given permission by owner to enter the garage to whiteness the test. Contact the contractor Greg Bouwer at ###-#### for any questions about gaining entrance. Phone #: ###-#### Inspection requested via web by David Dixon- 60lb gas pass- tagged gas line at meter bar- will need to see drip leg after shut off valve but before regulator and need to secure csst above unit heater flue vent with 6" clearance to csst by final- call in final when ready
|
MEC18-05760
| Final | 12/28/2018 | 12/28/2018 | 12/28/2018 2:29:28 PM | P | PASS |
|
|
Josh ###-####- furnace co ok
|
MEC18-05547
| Final | 12/28/2018 | 12/28/2018 | 12/28/2018 1:52:15 PM | P | PASS |
|
|
Inspection requested via web by Andrea Grigsby- furnace a/c coil co ok
|
MEC18-06098
| Final | 12/26/2018 | 12/28/2018 | 12/28/2018 1:19:07 PM | P | PASS |
|
|
INSTALLER AL ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- gas piping unit heater ok
|
MEC18-06098
| Pressure Test | 12/26/2018 | 12/28/2018 | 12/28/2018 1:18:20 PM | P | PASS |
|
|
INSTALLER AL ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 20lb gas pass
|
MEC18-06048
| Final | 12/21/2018 | 12/28/2018 | 12/28/2018 11:47:26 AM | A | PASS |
|
|
Please call Bruce or Janice Carruthers (###-####) 30 minutes prior to showing up, Thank you. Phone #: ###-#### Inspection requested via web by Tyler Collado- furnace co ok
|
MEC18-05698
| Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 11:27:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- missing transfers path for R/A both units to bedrooms
|
MEC18-05698
| Pressure Test | 12/28/2018 | 12/28/2018 | 12/28/2018 11:26:26 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass both units
|
MEC18-06116
| Pressure Test | 12/28/2018 | 12/28/2018 | 12/28/2018 11:25:45 AM | A | PASS |
|
|
20lb gas pass both units
|
MEC18-06116
| Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 11:25:16 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- missing transfer grills both units for R/A paths
|
MEC18-06001
| Pressure Test | 12/27/2018 | 12/28/2018 | 12/28/2018 10:01:03 AM | A | NR |
|
|
Rose ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- gas piping is not installed into fireplace looks like needs to be routed to other side- need to retest when installed- need to add other to permit for all ducting installed- need to submit manual j for approval- recall in gas test and R/I when ready
|
MEC18-05664
| Final | 12/28/2018 | 12/28/2018 | 12/28/2018 9:17:30 AM | A | PASS |
|
|
josh ###-####- furnace co ok
|
MEC18-06105
| Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 8:43:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace R/I ok
|
MEC17-03358
| Mec-Aging Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 8:17:27 AM | | CANC |
|
|
|
MEC17-03358
| DOC - Permit Expired | 12/28/2018 | 12/28/2018 | 12/28/2018 8:17:21 AM | A | PASS |
|
|
no calls
|
MEC18-01369
| Mec-Aging Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 8:16:59 AM | | FAIL |
|
|
still need corrections made to fireplace to final this permit out
|