BLD18-04417
| FIRE-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 4:17:46 PM | P | PART |
|
|
Previously noted items for life fire safety inspection have been completed. Phone lines for fire panel monitoring were effected by Century Link failure so fire panel was showing a communication failure, per conversation with Ron Johnson a fire watch is recommended and a 15 day TCO is authorized contingent on phone lines being repaired and fire sprinkler monitoring is established.
|
BLD17-04686
| FIRE-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 4:11:23 PM | P | FAIL |
|
|
Exposed combustible material in basement that is no covered by fire sprinklers. Need FIR permits for fire alarm and fire sprinkler finaled before life safety can be completed. Install sheetrock in level 1 elevator lobby, sprinkler head not installed because of no sheetrock. Provide signage for exterior showing which stairwell has roof top access and the one that does not. Still need to test emergency lighting.
Mop sink on level 4 leaked down to level 3 saturating the monitoring modules for the fire alarm system, leak needs to be fixed to prevent false alarms.
Pete Phone #: ###-####
|
FIR18-00420
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 3:21:43 PM | P | FAIL |
|
|
Multiple heads blocked in basement level. Could not test basement flow switch due to sump pump no keeping up with water flow. Exposed combustible material in basement level with no sprinkler protection.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00162
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 3:20:28 PM | P | FAIL |
|
|
Did not have basement city approved drawings, horn strobe in basement was inoperable but couldn't tell if it was part of the TI system or part of core and shell.
derik Phone #: ###-####
|
FIR18-00741
| INSP-Final Inspection | 12/28/2018 | 12/28/2018 | 12/28/2018 3:19:19 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Please call Lonnie before heading over to the project for the final inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
BLD18-01913
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 12:16:38 PM | A | PASS |
|
|
Smoke detector has been placed in bedroom, final life fire safety inspection for area of work complete.
Heidi Phone #: ###-####
|
BLD18-01064
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 12:03:35 PM | P | FAIL |
|
|
Fire alarms are not complete, need fire alarms for phase 2 finaled. Phase 2 is not ready for life fire safety inspection.
Dave-2nd floor of phase 2 Phone #: ###-####
|
FIR18-00455
| INSP-Alarm Testing | 12/28/2018 | 12/28/2018 | 12/28/2018 12:02:00 PM | P | FAIL |
|
|
Provide3 notification in area between offices on southwest corner. Provide correct coverage in restrooms, currently restrooms have shadow issues. Clean up wiring on NAC panels, can't have wires hanging out of panel.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00382
| INSP-Sprinkler Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 11:59:46 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in phase 3 kitchen area and soffit in expansion area complete, approved for cover.
Rough to cover, server area - Zach Phone #: ###-####
|
FIR18-00684
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 11:05:14 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00708
| INSP-Sprinkler Rough-in | 12/26/2018 | 12/28/2018 | 12/28/2018 11:04:25 AM | A | PART |
|
|
Rough to cover inspection for overhead firte sprinkler piping on level 1 restroom/gym area complete. RTC for grid areas on level 1 complete, areas inspected approved for cover.
Contact is Mike Martin. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00708
| INSP-Sprinkler Rough-in/Hydro | 12/27/2018 | 12/28/2018 | 12/28/2018 11:03:15 AM | A | DONE |
|
|
Hydrostatic test for level 1 witnessed, nio pressure loss observed.
Mike Phone #: ###-####
|
FIR18-00583
| INSP-Final Inspection | 12/26/2018 | 12/28/2018 | 12/28/2018 11:01:34 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 2 complete.
Mike Martin is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00455
| INSP-Alarm Testing | 12/27/2018 | 12/28/2018 | 12/28/2018 9:40:44 AM | A | CANC |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, December 28, 2018.
|
FIR18-00826
| INSP-Sprinkler Rough-in | 12/28/2018 | 12/28/2018 | 12/28/2018 9:36:49 AM | A | PART |
|
|
Rough to cover inspection for overehad fire sprinkler piping/tenting on north apartment units complete, approved for cover except unit B-HC on level 3, mentioned unit cannot be covered due to tenting issues.
|
FIR18-00826
| INSP-Sprinkler Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 9:33:40 AM | A | FAIL |
|
|
Unit B-HC level 3 has exposed piping in the attis space where tenting was not installed correctly.
2nd half inspection. Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00799
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 9:02:08 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
as per phone conversation
|
FIR18-00872
| INSP-Sprinkler Rough-in | 12/28/2018 | 12/28/2018 | 12/28/2018 9:00:49 AM | A | PASS |
|
|
Rouh to cover inspection for overehad fire sprinkler piping in area of work complete, area of work approved for cover.
|
FIR18-00872
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 8:59:35 AM | A | CANC |
|
|
Project not ready for final inspection. This request is cancelled.
Jim Baker is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03965
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 8:47:16 AM | A | PART |
|
|
Previously noted items have been completed except the fire alarm issue. 30 day TCO authorized by Ron Johnson for life fire safety contingent on fire alarm modification be completed.
Phone #: ###-#### Inspection requested via web by Tyson Jardine
|
BLD18-04372
| FIRE-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 8:35:36 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Zach Phone #: ###-####
|
FIR18-00420
| INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/27/2018 3:42:28 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis
|