Inspections for the day of: Wednesday, December 29, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01700 FIRE-Final Inspection12/28/200412/29/200412/29/2004 12:00:00 AMAFAIL
Dave- Suite 100; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need fire code review notes; install exit sign at vestibule per plans; need to verify exit/emergency lights on battery; provide extinguishers; install sprinkler escutcheons; provide sprinkler resubmittals; exit sign at lobby area - remove arrow; duct detectors may be required will verify with plan review notes - no mechanical plans 12/29/2004 8:47:02 AM
BLD04-01762 FIRE-Final Inspection12/28/200412/29/200412/29/2004 12:00:00 AMAFAIL
George-call 1/2 hr before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice Emergency light needed per plans; door 101 has deadbolt 12/29/2004 9:15:42 AM
BLD04-02015 FIRE-Conference12/28/200412/29/200412/29/2004 12:00:00 AMAPART
###-####-- please call 1/2 before going out Met with GC - fire extinguishers on both levels and exit signs per plans 12/29/2004 11:08:29 AM
BLD04-02051 FIRE-Sprinkler Rough-in12/29/200412/29/200412/29/2004 12:00:00 AMPPASS
ted; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Okay to cover 12/29/2004 2:32:57 PM
BLD04-01937 FIRE-Final Inspection12/29/200412/29/200412/29/2004 12:00:00 AMPFAIL
Joshua; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need extinguisher with tags; door openable from the inside without special knowledge per plan review notes; sign above door 12/29/2004 1:47:32 PM
FIR04-00716 INSP-Final Inspection12/29/200412/29/200412/29/2004 12:00:00 AMPPASS
Spacing maintained at 196 sq ft 12/29/2004 2:32:29 PM
FIR03-00690 INSP-Final Inspection12/27/200412/29/200412/29/2004 12:00:00 AMPFAIL
cliff; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Stopped inspection - room sounder bases didn't sound on general alarm; re-inspection fee will be added and must be paid prior to another inspection 12/29/2004 5:33:27 PM
BLD04-02784 FIRE-Final Inspection12/28/200412/29/200412/29/2004 12:00:00 AMPDONE
Scheduled by a contractor via Hello! on 12/28/2004 at 10:39:03 AM. Contact: ###-####. Fire not required to sign-off; sent to 415 12/29/2004 7:56:38 AM
BLD04-01827 FIRE-Final Inspection12/28/200412/29/200412/29/2004 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 12/28/2004 at 11:03:28 AM. Contact: ###-####. Per GC - not ready and this will be rescheduled for another day 12/29/2004 3:53:41 PM