FIR04-00608
| INSP-Sprinkler Rough-in | 12/28/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | A | PART |
|
|
Sprinkler rough-in ok except for compliance with notes 89 and 91of review comments, hangers on bottom chord and hung on a single truss. Piping in canopies is allso laying on the bottom chord. This needs changed or provide engineering verification. Pipe straps in the canopies are spaced up to 22' apart in some locations. 18' in others. This does not meet nfpa 13 table 9.2.2.1. Provide canopies that are missing. Lower pendant in dbsi's office as shown on plans. Replace bent pendants in dbsi's space. Relocate pendants that are too close to wall in dbsi's space. Complete all other items on review notes such as forward flush, hydro test ect. 12/29/2004 11:12:24 AM
|
BLD04-02759
| FIRE-Final Inspection | 12/28/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 12/29/2004 11:01:51 AM
|
FIR04-00763
| INSP-Final Inspection | 12/28/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/28/2004 at 4:50:02 PM. Contact: ###-####.
|
FIR04-00627
| INSP-Sprinkler Rough-in | 12/29/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | P | PART |
|
|
Ok to cover underground supply piping that is located under the roadway only. Per Terry the installer there will be two additional 45 degree elbows in the underground. Resubmitt plans showing these additional valves or provide verification Bill won't require resubmittals. 12/29/2004 1:31:57 PM
|
FIR04-00469
| INSP-Final Inspection | 12/29/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | P | PASS |
|
|
Contact: Chris Felty - Please call with time that can meet, would like to do around 10 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR04-00772
| INSP-Final Inspection | 12/29/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | P | PASS |
|
|
Bruce; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
BLD04-02511
| FIRE-Final Inspection | 12/29/2004 | 12/29/2004 | 12/29/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled
|