Inspections for the day of: Thursday, December 29, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00425 INSP-Sprinkler Rough-in/Hydro12/28/200512/29/200512/29/2005 2:53:13 PMPFAIL
Air test failed, some items on rough-in c/n for the dry garage systems not complete including two EQ braces, high temp head, branch lines not installed, hanger, listing for valves at one drum drip.
FIR05-00837 INSP-Final Inspection12/29/200512/29/200512/29/2005 2:16:28 PMPPASS
Fire alarm is acceptable for the first floor TI space.
FIR05-00848 INSP-Final Inspection12/29/200512/29/200512/29/2005 1:35:16 PMPCANC
Forrest, We would like to schedule this for late this afternoon. 1st floor only. Call if their are any problems. Thanks Jason or Mike; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
MIS05-00236 FIR-Final12/29/200512/29/200512/29/2005 12:27:56 PMPPASS
Life safety is satisfactory, discussed requirements for possible future remodel.
FIR05-00471 INSP-Final Inspection12/28/200512/29/200512/29/2005 11:22:31 AMAFAIL
Smoke alarms in the SW tenant are not interconnected, new strobes on the first floor are not synchronized.
BLD05-02726 FIRE-Final Inspection12/28/200512/29/200512/29/2005 9:48:45 AMAPASS
c/n items are complete, no signature card available on site.