FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 12/28/2005 | 12/29/2005 | 12/29/2005 2:53:13 PM | P | FAIL |
|
|
Air test failed, some items on rough-in c/n for the dry garage systems not complete including two EQ braces, high temp head, branch lines not installed, hanger, listing for valves at one drum drip.
|
FIR05-00837
| INSP-Final Inspection | 12/29/2005 | 12/29/2005 | 12/29/2005 2:16:28 PM | P | PASS |
|
|
Fire alarm is acceptable for the first floor TI space.
|
FIR05-00848
| INSP-Final Inspection | 12/29/2005 | 12/29/2005 | 12/29/2005 1:35:16 PM | P | CANC |
|
|
Forrest, We would like to schedule this for late this afternoon. 1st floor only. Call if their are any problems. Thanks Jason or Mike; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
MIS05-00236
| FIR-Final | 12/29/2005 | 12/29/2005 | 12/29/2005 12:27:56 PM | P | PASS |
|
|
Life safety is satisfactory, discussed requirements for possible future remodel.
|
FIR05-00471
| INSP-Final Inspection | 12/28/2005 | 12/29/2005 | 12/29/2005 11:22:31 AM | A | FAIL |
|
|
Smoke alarms in the SW tenant are not interconnected, new strobes on the first floor are not synchronized.
|
BLD05-02726
| FIRE-Final Inspection | 12/28/2005 | 12/29/2005 | 12/29/2005 9:48:45 AM | A | PASS |
|
|
c/n items are complete, no signature card available on site.
|