Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00611 INSP-Final Inspection12/29/200612/29/20061/2/2007 11:27:12 AMPPASS
Per field inspection completed by M. Timmerman, alarm work is satisfactory, permit finaled.
FIR05-00695 INSP-Alarm Testing12/29/200612/29/200612/29/2006 4:29:43 PMPDEFR
Rob ###-#### Note: 9th floor Not enough time available with todays schedule that an entire floor inspeciton could be completed. Inspection rescheduled for next week.
FIR06-00849 INSP-Final Inspection12/29/200612/29/200612/29/2006 4:27:22 PMPPASS
Noted that no inspection for cover had been requested or completed prior to final. However, the shop owner removed enough ceiling tile while on site that an adequate installation inspection was completed and the permit could be finaled.
FIR06-00961 INSP-Final Inspection12/28/200612/29/200612/29/2006 4:22:56 PMPPASS
Fire alarm permit finaled.
BLD06-02719 FIRE-Final Inspection12/29/200612/29/200612/29/2006 4:13:32 PMPFAIL
Missing emergency lighting as indicated on approved plans and per fire code review notes, the sample tube in the duct detector is incorrect.
FIR06-00870 INSP-Sprinkler Rough-in12/28/200612/29/200612/29/2006 2:49:46 PMAPART
Fire sprinkler work is approved, permit is ready for final when requested.
FIR06-00092 INSP-Sprinkler Rough-in12/28/200612/29/200612/29/2006 2:48:22 PMAPART
Overhead rough-in as cirlced and dated on the approved plans in the SW corner of the TI is okay for cover at the drop ceilings.
FIR06-00692 INSP-Sprinkler Rough-in12/27/200612/29/200612/29/2006 2:46:53 PMAFAIL
Heads are overspaced in the hallway adjacent to the relocated heads.
FIR06-00705 INSP-Sprinkler Rough-in12/27/200612/29/200612/29/2006 2:45:45 PMAFAIL
Need to relocate one head and remove the head piped via mechanical tee from the drain line piping.
BLD06-01211 FIRE-Final Inspection12/28/200612/29/200612/29/2006 1:10:18 PMPPASS
Required corrections have been made, life safety inspection passed.
FIR06-00063 INSP-Final Inspection12/28/200612/29/200612/29/2006 1:09:08 PMAPASS
Fire sprinkler permitted work passed final inspection.
BLD06-00203 FIRE-Final Inspection12/28/200612/29/200612/29/2006 1:08:06 PMAPASS
Fire life safety is acceptable, noted one extinguisher at the mech. mezzanine is to be mounted on the wall as discussed prior to structural final.
BLD06-02026 FIRE-Final Inspection12/28/200612/29/200612/29/2006 1:05:58 PMAPASS
Fire life safety final inspection passed.
FIR06-00555 INSP-Final Inspection12/28/200612/29/200612/29/2006 1:05:18 PMAPASS
Fire sprinkler work is satisfactory, inspection passed, permit finaled.
BLD06-02415 FIRE-Final Inspection12/28/200612/29/200612/29/2006 11:05:59 AMAPASS
Items on previous c/n have been completed, final life safety inspection passed.
BLD06-00824 FIRE-Final Inspection12/28/200612/29/200612/29/2006 10:50:59 AMAPASS
Fire life safety inspection passed.
FIR06-00846 INSP-Final Inspection12/28/200612/29/200612/29/2006 10:05:45 AMAPASS
Fire sprinkler permit finaled.