FIR08-00626
| INSP-Sprinkler Rough-in/Hydro | 12/29/2008 | 12/29/2008 | 12/29/2008 6:07:33 PM | P | PART |
|
|
The rough-in inspection for the 3" and 2 1/2" mains and 1 1/4" branchline piping passed. Pendant head locations have not been inspected at this time. Per the fitter plans are being resubmitted for pendant head location changes due to revised wall layout. I noted sprinkler coverage missing in four shower areas.
|
FIR08-00341
| INSP-Alarm Testing | 12/24/2008 | 12/29/2008 | 12/29/2008 2:40:16 PM | A | FAIL |
|
|
Need the north red alarm strobe repaired and tested, the new duct smoke detector does not shut down the hvac unit and the fire alarm system needs to be finished in the existing east rooms.
|
FIR08-00299
| INSP-Final Inspection | 12/24/2008 | 12/29/2008 | 12/29/2008 2:21:23 PM | A | PASS |
|
|
Permit finaled.
|
BLD08-01889
| FIRE-Final Inspection | 12/24/2008 | 12/29/2008 | 12/29/2008 12:11:01 PM | A | PASS |
|
|
Life safety passed. Contractor is to have the three thumbturn deadbolts blanked off on all exit doors and lever hardware installed on the northwest exit door. This is to be done prior to the building inspection.
|