FIR10-00257
| INSP-Final Inspection | 12/28/2010 | 12/29/2010 | 12/29/2010 3:35:43 PM | A | PART |
|
|
Added EC heads okayed and verified per resubmitals. Final walkthrough passed with the exception of three areas in need of revision including provide matched temp. heads at the second floor stairway, amend blocked coverage at the main entry lobby, add protection under a new raised equipment access deck at the attic space.
|
FIR10-00599
| INSP-Final Inspection | 12/28/2010 | 12/29/2010 | 12/29/2010 3:30:14 PM | A | PASS |
|
|
C/N items finished, re-inspection passed. Final okay pending scanable as-built record drawings are provided including an accurate map at the panel.
|
BLD10-02878
| FIRE-Final Inspection | 12/28/2010 | 12/29/2010 | 12/29/2010 3:27:23 PM | A | PASS |
|
|
Re-inspection passed. Life safety final approved.
|
BLD10-02327
| FIRE-Final Inspection | 12/28/2010 | 12/29/2010 | 12/29/2010 3:25:38 PM | A | PASS |
|
|
Items on correction notice verified for completion. Life safety passed.
|
BLD10-00735
| FIRE-Final Inspection | 12/29/2010 | 12/29/2010 | 12/29/2010 3:23:34 PM | P | PASS |
|
|
Correction items finished. Fire life safety finaled.
|
BLD10-01629
| FIRE-Final Inspection | 12/28/2010 | 12/29/2010 | 12/29/2010 3:21:53 PM | A | PASS |
|
|
Fire life safety completed acceptable, inspection passed.
|
FIR10-00557
| INSP-Final Inspection | 12/27/2010 | 12/29/2010 | 12/29/2010 3:20:01 PM | A | PASS |
|
|
Scope of fire alarm work passed inspection, permit finaled.
|