Inspections for the day of: Monday, December 29, 2014.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01597 Final12/29/201412/29/201412/29/2014 2:50:52 PMPFAIL
Shane is the contact his cell no. ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
517.18 B Patient bed location receptacles shall be listed hospital grade receptacles and shall be so identified
422.31 disconnecting means shall be provided for all permanently installed appliances
408.4 circuit shall be legibly identified
110.16 arc flash warning labels required for panelboards and switchgear
ELE14-02950 Final12/29/201412/29/201412/29/2014 1:10:44 PMPPASS
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
final ok
ELE14-03505 Electrical Rough-In12/28/201412/29/201412/29/2014 12:45:11 PMPPASS
Access from alley Phone #: ###-#### Inspection requested via web by Brad Girard
RI OK
ELE14-02762 Electrical Rough-In12/29/201412/29/201412/29/2014 12:23:10 PMPPASS
Underground inspection; (3) sawcuts Phone #: ###-#### Inspection requested via web by Steve McCloy
UG conduit ok to cover
ELE14-02938 Final12/29/201412/29/201412/29/2014 8:56:00 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
corrections made, final ok
ELE14-00076 Final12/29/201412/29/201412/29/2014 8:34:52 AMAPASS
Homeowner will be there this morning.
patio was enclosed and is ready. Phone #: ###-#### Inspection requested via web by Mike Cole
Final OK