Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00554 INSP-Final Inspection12/29/201412/29/201412/29/2014 3:27:34 PMPCANC
Richard is your contact. Please call 45 mins prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR14-00420 INSP-Sprinkler Rough-in/Hydro12/29/201412/29/201412/29/2014 3:26:00 PMPPASS
over head hydro test passed
BLD14-02856 FIRE-Final Inspection12/29/201412/29/201412/29/2014 2:35:25 PMPPASS
Life safety passed. Sprinkler protection not required for the new storefront (CMU separation with no penatration)
BLD14-02878 FIRE-Final Inspection12/29/201412/29/201412/29/2014 2:34:10 PMPPASS
Life safety passed
1-9-15-as per Troy Cobbley-alram and sprinklers are good permit is on 3085 N Cole so issue perm c of o CAN
FIR14-00888 INSP-Final Inspection12/28/201412/29/201412/29/2014 1:20:13 PMAFAIL
See alarm testing inspection for today for list of correction items needed.
FIR14-00888 INSP-Alarm Testing12/28/201412/29/201412/29/2014 1:19:39 PMADONE
Tested function of the horn/strobes. Need as-builts showing the adjustment of the candella's and the addition of the duct smoke detector. And then testing of the duct smoke detector. Need weather proof backbox for the strobe over the pool. "Water Bug" may not be listed for use with acid.