ELE13-01393
| ELE-Aging Inspection | 12/29/2015 | 12/29/2015 | 12/29/2015 2:35:25 PM | | FAIL |
|
|
Unable to confirm listing
|
ELE13-01500
| Final | 12/29/2015 | 12/29/2015 | 12/29/2015 2:34:27 PM | P | PASS |
|
|
UL listing confirmed. Final ok
|
ELE15-04096
| Final | 12/28/2015 | 12/29/2015 | 12/29/2015 2:28:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
|
ELE15-03386
| Final | 12/28/2015 | 12/29/2015 | 12/29/2015 2:09:11 PM | A | FAIL |
|
|
Call before you go for the code. Phone #: ###-#### Inspection requested via web by Greg Idsinga 210.8(B)(5)- All 120 volt receptacle outlets installed with in 6' of a sink shall have GFCI protection. 210.62- At least one 120 volt single phase 15 or 20 amp receptacle outlets shall be installed for each show window 6' or wider on store front.
|
ELE15-02615
| Final | 12/29/2015 | 12/29/2015 | 12/29/2015 1:54:59 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson No card posted. ETL listing on over chair luminaires. Final ok
|
ELE15-03468
| Final | 12/29/2015 | 12/29/2015 | 12/29/2015 1:24:52 PM | P | PASS |
|
|
Electrical final. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Final ok
|
ELE15-04114
| Electrical Rough-In | 12/29/2015 | 12/29/2015 | 12/29/2015 12:26:58 PM | P | PASS |
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley Basement and kitchen areas only rewired. All existing receptacles had equipment grounds ran seperate from old NM cable. All grounding taps not good do to whole house replumbed with plastic pipe. Contractor to address grounding type receptacles at future time. Rough in ok cover
|
ELE15-04114
| Permanent Service | 12/29/2015 | 12/29/2015 | 12/29/2015 11:12:40 AM | P | PASS |
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley p/s o/h rec ok
|
ELE15-03867
| Final | 12/29/2015 | 12/29/2015 | 12/29/2015 11:08:56 AM | A | PASS |
|
|
call for access code Phone #: ###-#### Inspection requested via web by Rick Beckman Final ok
|
ELE15-04114
| Electrical Rough-In | 12/28/2015 | 12/29/2015 | 12/29/2015 8:53:12 AM | A | FAIL |
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface, secure NM 1 1/4" from framing surface. Existing and new. 408.7- Unused breaker spaces shal be closed. Verbal with Troy
|