Inspections for the day of: Tuesday, December 29, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01393 ELE-Aging Inspection12/29/201512/29/201512/29/2015 2:35:25 PM FAIL
Unable to confirm listing
ELE13-01500 Final12/29/201512/29/201512/29/2015 2:34:27 PMPPASS
UL listing confirmed. Final ok
ELE15-04096 Final12/28/201512/29/201512/29/2015 2:28:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson
Final ok
ELE15-03386 Final12/28/201512/29/201512/29/2015 2:09:11 PMAFAIL
Call before you go for the code. Phone #: ###-#### Inspection requested via web by Greg Idsinga
210.8(B)(5)- All 120 volt receptacle outlets installed with in 6' of a sink shall have GFCI protection.
210.62- At least one 120 volt single phase 15 or 20 amp receptacle outlets shall be installed for each show window 6' or wider on store front.
ELE15-02615 Final12/29/201512/29/201512/29/2015 1:54:59 PMPPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
No card posted. ETL listing on over chair luminaires. Final ok
ELE15-03468 Final12/29/201512/29/201512/29/2015 1:24:52 PMPPASS
Electrical final. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Final ok
ELE15-04114 Electrical Rough-In12/29/201512/29/201512/29/2015 12:26:58 PMPPASS
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley Basement and kitchen areas only rewired. All existing receptacles had equipment grounds ran seperate from old NM cable. All grounding taps not good do to whole house replumbed with plastic pipe. Contractor to address grounding type receptacles at future time. Rough in ok cover
ELE15-04114 Permanent Service12/29/201512/29/201512/29/2015 11:12:40 AMPPASS
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley p/s o/h rec ok
ELE15-03867 Final12/29/201512/29/201512/29/2015 11:08:56 AMAPASS
call for access code Phone #: ###-#### Inspection requested via web by Rick Beckman Final ok
ELE15-04114 Electrical Rough-In12/28/201512/29/201512/29/2015 8:53:12 AMAFAIL
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface, secure NM 1 1/4" from framing surface. Existing and new.
408.7- Unused breaker spaces shal be closed.
Verbal with Troy