Inspections for the day of: Monday, December 3, 2001.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC01-03559 Pressure Test11/27/200112/3/200112/3/2001 12:00:00 AMAPASS
###-#### only gas line
MEC01-02579 Rough-in11/30/200112/3/200112/3/2001 12:00:00 AMAPART
duct ok, doors needed at fire dampers and smoke fire dampers 12/3/2001 9:30:25 AM
MEC01-03512 Rough-in12/3/200112/3/200112/3/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/03/2001 at 07:37:28. Contact: ###-####.
MEC01-03512 Pressure Test12/3/200112/3/200112/3/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/03/2001 at 07:38:11. Contact: ###-####.
MEC01-03164 Final12/3/200112/3/200112/3/2001 12:00:00 AMPFAIL
pop off drain at water heater is trapped, need to replace so 1/8" hole can be drilled in bottom of drain line at water heater 12/3/2001 2:24:25 PM
MEC01-01783 Final12/3/200112/3/200112/3/2001 12:00:00 AMPFAIL
need full 1" supply gas pipe at both sets of furn. and water heaters. have 3/4" NOW 12/3/2001 1:27:18 PM
MEC01-03622 Pressure Test12/3/200112/3/200112/3/2001 12:00:00 AMPPASS
mike ###-#### pres test