FIR02-00332
| INSP-Final Inspection | 12/3/2002 | 12/3/2002 | 12/3/2002 12:00:00 AM | A | FAIL |
|
|
relocate the smoke detector above the FACP to the deck, provide the correct battery size, provide the correct Boise Fire Dept. approved knox key box, provide lock on breaker and paint, neither phone line give a trouble when disconnected. I stopped the inspection. No other items looked at or tested
|
BLD02-00955
| FIRE-Final Inspection | 12/3/2002 | 12/3/2002 | 12/3/2002 12:00:00 AM | P | FAIL |
|
|
sprinklers are now correct but the duct smoke detector needs to have the correct type of wire installed 12/3/2002 2:48:02 PM
|