ELE04-03763
| Rough-In Permanent Service | 12/1/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | PASS |
|
|
steve- ###-#### called contr. and told he needed about 5 nailplates and that BCC requires outside wire to be made up. ok to cover. p/s u/g n ok 12/3/2004 10:07:55 AM
|
ELE04-03786
| Temporary Service | 12/2/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | PASS |
|
|
###-#### - aaron t/s u/g n ok 12/3/2004 8:18:41 AM
|
ELE04-03790
| Electrical Rough-In | 12/2/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | PASS |
|
|
###-#### - andy called elect and said to move closet light, ok to cover. 12/3/2004 9:21:06 AM
|
ELE04-03789
| Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice 330.30(C) MC cable shall be strapped within 12" of box 12/3/2004 4:18:55 PM
|
ELE04-03794
| Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
Rick-call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to cover, kitchen 12/3/2004 2:36:12 PM
|
ELE04-03795
| Temporary Service | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
###-#### - dan t/s u/g n ok 12/3/2004 1:53:31 PM
|
ELE04-03178
| Final | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final 12/3/2004 3:06:31 PM
|
ELE04-03800
| Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
John-Wall only; Phone #: ###-#### Internet Inspection Request from: Jan Rice 330.30(C) MC cable shall be strapped within 12" of box, 110.3(B) shall use correct strap on conduit, 250.92(B) shall use bonding type locknut thru concentric 12/3/2004 4:23:17 PM
|
ELE04-03802
| Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
rick ###-#### ok to cover bathroom walls 12/3/2004 1:31:16 PM
|