BLD04-00479
| FIRE-Final Inspection | 12/2/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 12/3/2004 10:28:13 AM
|
BLD03-02433
| FIRE-Final Inspection | 12/2/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 12/3/2004 10:28:24 AM
|
FIR04-00679
| INSP-Final Inspection | 12/2/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | A | FAIL |
|
|
nozzles exceed 16" from centerline of the hazard and exceed the 40"-48" from the cooking surface. No test performed. 12/3/2004 8:52:33 AM
|
FIR04-00732
| INSP-Alarm Testing | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
Relocate duct smoke detector as discussed and re-test 12/3/2004 3:41:16 PM
|
FIR04-00679
| INSP-Sprinkler Rough-in/Hydro | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
Need air balance report for hood 12/3/2004 2:37:02 PM
|
BLD04-01191
| FIRE-Final Inspection | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
Need air balance report for hood 12/3/2004 2:37:15 PM
|
FIR04-00348
| INSP-Final Inspection | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinklers finaled 12/3/2004 2:38:45 PM
|
FIR04-00703
| INSP-Final Inspection | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled
|
BLD04-02507
| FIRE-Final Inspection | 12/3/2004 | 12/3/2004 | 12/3/2004 12:00:00 AM | P | FAIL |
|
|
Need to provide emergency light at the main exit as per plans. Provide listed emergency light at the main exit discharge as per plans. Final fire alarm permit.
|