Inspections for the day of: Friday, December 3, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00479 FIRE-Final Inspection12/2/200412/3/200412/3/2004 12:00:00 AMAPASS
Fire life safety finaled 12/3/2004 10:28:13 AM
BLD03-02433 FIRE-Final Inspection12/2/200412/3/200412/3/2004 12:00:00 AMAPASS
Fire life safety finaled 12/3/2004 10:28:24 AM
FIR04-00679 INSP-Final Inspection12/2/200412/3/200412/3/2004 12:00:00 AMAFAIL
nozzles exceed 16" from centerline of the hazard and exceed the 40"-48" from the cooking surface. No test performed. 12/3/2004 8:52:33 AM
FIR04-00732 INSP-Alarm Testing12/3/200412/3/200412/3/2004 12:00:00 AMPFAIL
Relocate duct smoke detector as discussed and re-test 12/3/2004 3:41:16 PM
FIR04-00679 INSP-Sprinkler Rough-in/Hydro12/3/200412/3/200412/3/2004 12:00:00 AMPFAIL
Need air balance report for hood 12/3/2004 2:37:02 PM
BLD04-01191 FIRE-Final Inspection12/3/200412/3/200412/3/2004 12:00:00 AMPFAIL
Need air balance report for hood 12/3/2004 2:37:15 PM
FIR04-00348 INSP-Final Inspection12/3/200412/3/200412/3/2004 12:00:00 AMPPASS
Fire sprinklers finaled 12/3/2004 2:38:45 PM
FIR04-00703 INSP-Final Inspection12/3/200412/3/200412/3/2004 12:00:00 AMPPASS
fire sprinklers finaled
BLD04-02507 FIRE-Final Inspection12/3/200412/3/200412/3/2004 12:00:00 AMPFAIL
Need to provide emergency light at the main exit as per plans. Provide listed emergency light at the main exit discharge as per plans. Final fire alarm permit.