Inspections for the day of: Monday, December 3, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00487 ELE-Aging Inspection12/3/200712/3/200712/6/2007 9:55:39 AM PART
wsuc waiting for contr to call
ELE07-02982 Final12/3/200712/3/200712/3/2007 4:25:49 PMPFAIL
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
called left message needs clearence downstairs closet lights
ELE07-03989 Final12/3/200712/3/200712/3/2007 3:39:10 PMPPASS
tom Phone #: ###-####
ELE06-04453 Final12/3/200712/3/200712/3/2007 3:13:43 PMPPASS
Loren, please call 1sr for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
ELE07-03789 Electrical Rough-In12/3/200712/3/200712/3/2007 2:47:16 PMPFAIL
dale Note: please call 1/2 hr prior to inpsection so he show where to see Phone #: ###-#### corr called 300.4 nail plates, 300.14 needs 6" free length, 110.14(B) needs splicing devices wires just twisted together, 210.70 lights for outside exits, and accessible attic, 110.3(B) needs main breaker and backfed clip shop p/s needs 2 grd rods, 250.32, 250.119(A) shall not ID #6 or smaller equip grd
ELE07-03789 Electrical Rough-In12/3/200712/3/200712/3/2007 2:43:00 PMPPART
dale Note: please call 1/2 hr prior to inpsection so he show where to see Phone #: ###-#### u/g ok only
ELE07-03983 Temporary Service12/3/200712/3/200712/3/2007 2:05:42 PMPPASS
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery t/s u/g new ok
ELE07-03982 Electrical Rough-In12/3/200712/3/200712/3/2007 1:31:17 PMPPASS
jay - ###-#### r/i ok needs 15 amp for jtub circuits, and use only manufactures listed breakers called
ELE07-03971 Electrical Rough-In12/3/200712/3/200712/3/2007 12:45:29 PMPPART
Stu, this uis for Su. 100; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls, and hard ceiling rest rm
ELE07-03971 Permanent Service12/3/200712/3/200712/3/2007 12:44:31 PMPPASS
Stu, this uis for Su. 100; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g new for meter
ELE07-00358 Final12/3/200712/3/200712/3/2007 11:48:40 AMAPASS
ELE07-02903 Final12/3/200712/3/200712/3/2007 10:44:07 AMAPASS
Thank You!! Phone #: ###-#### Internet Inspection Request from: Tracy
ok no card
ELE07-03907 Temporary Service12/3/200712/3/200712/3/2007 9:45:44 AMAFAIL
Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery called needs seperate permit for t/s
ELE07-03888 Electrical Rough-In11/30/200712/3/200712/3/2007 9:25:51 AMAFAIL
Please call at least 20 mins prior to inspection-Ron holden Phone #: ###-####
300.4 nail plates and 11/4", 110.3(B) p/s at shop needs main breaker, 314.23 &B C C no cutin boxes for new construction, needs conn for GEC, B C C complete all makeup, 314.3 needs bond bushing metal raceway in plastic jbox at house, 352.12(C) needs schedule 80 for exposed sections of PVC, grd to concrete encased electrode
ELE07-03905 Electrical Rough-In11/30/200712/3/200712/3/2007 8:26:09 AMAPART
craig Note: wall Phone #: ###-####
walls ok