Inspections for the day of: Wednesday, December 3, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01749 FIRE-Final Inspection12/3/200812/3/200812/3/2008 5:00:14 PMPPASS
BLD08-00204 FIRE-Final Inspection12/3/200812/3/200812/3/2008 4:19:27 PMPPASS
Vanilla permit fire life safety inspection passed.
FIR07-01031 INSP-Sprinkler Rough-in12/3/200812/3/200812/3/2008 4:17:33 PMPFAIL
Inspection for cover at the 1st floor lobby 09 and the 2nd floor conference room 327 failed due to field modificaitons beyond the limits of in field approvals via as-built plans- noted pipe size, branchline and head number inconsistencies.
FIR08-00544 INSP-Sprinkler Rough-in12/2/200812/3/200812/3/2008 2:46:46 PMPPART
Okay to cover pendent heads at the new entry vestibule, one additional pendent at the reception area soffit also okayed.
FIR08-00756 INSP-Sprinkler Rough-in12/3/200812/3/200812/3/2008 2:40:47 PMPPART
Overhead fire sprinkler system modifications are approved for cover at both suite 211 and 210. NOTE: one missing retaining strap at an existing beam clamp to be attatched prior to final-circled location on plan.
BLD08-00205 FIRE-Final Inspection12/2/200812/3/200812/3/2008 1:18:52 PMAPASS
Vanilla permit fire life safety is satisfactory, foil at one upright fire sprinkler head to be removed promptly per contractor.
BLD08-02492 FIRE-Final Inspection12/2/200812/3/200812/3/2008 1:17:04 PMAFAIL
Provide missing fire extinguisher and post as discussed with a current certification tag, provide approved door hardware at the restroom.
BLD08-02063 FIRE-Final Inspection12/2/200812/3/200812/3/2008 1:14:09 PMAPASS
Fire life safety inspection passed.
FIR08-00744 INSP-Final Inspection12/3/200812/3/200812/3/2008 10:37:44 AMPPASS
Fire sprinkler work passed final inspection.
BLD08-01872 FIRE-Final Inspection12/2/200812/3/200812/3/2008 10:12:09 AMAPASS
Correction notice completed, fire life safety finaled.