FIR08-00602
| INSP-Final Inspection | 12/3/2008 | 12/3/2008 | 12/3/2008 7:18:46 PM | P | CANC |
|
|
Due to limited time, the inspection turned into a conference. We are going to meet in the morning at 8:00am to begin the inspection.
|
BLD08-01056
| FIRE-Final Inspection | 12/2/2008 | 12/3/2008 | 12/3/2008 2:58:35 PM | A | CANC |
|
|
Request for Life and Saftey- please allow 30 min lead time as I will be working at my office. Thank You.... Phone #: ###-#### Internet Inspection Request from: Nick Downing
|
BLD08-00418
| FIRE-Final Inspection | 12/2/2008 | 12/3/2008 | 12/3/2008 2:58:18 PM | A | FAIL |
|
|
See the front sheet of the city approved drawings for the required corrections which include providing the missing fire hydrant, repair the exit discharge light at the main exit, provide emergency lighting in the main lobby, repair the area of refuge sign on the second floor, provide the area of refuge communication equipment and signage, provide the occupant load sign, mount fire extinguishers and provide the fire lane signage. Also the duct smoke detectors need to be replaced with spot type detectors that are listed for the air flow. These detectors are for damper operation.
|
FIR08-00573
| INSP-Final Inspection | 12/3/2008 | 12/3/2008 | 12/3/2008 2:57:04 PM | P | PASS |
|
|
Permit finaled per Ken Roule
|
BLD08-01011
| FIRE-Final Inspection | 12/2/2008 | 12/3/2008 | 12/3/2008 11:48:26 AM | A | PASS |
|
|
Life safety passed
|
FIR08-00645
| INSP-Sprinkler Rough-in/Hydro | 12/2/2008 | 12/3/2008 | 12/3/2008 11:29:27 AM | A | PASS |
|
|
underground hydro test passed for both the supply and the FDC
|
BLD08-02480
| FIRE-Final Inspection | 12/2/2008 | 12/3/2008 | 12/3/2008 11:24:48 AM | A | FAIL |
|
|
Repair exit signs/emergency lights, provide a fire extinguisher for the mezzanine, provide stickers at the exit doors.
|
FIR08-00701
| INSP-Sprinkler Rough-in/Hydro | 12/2/2008 | 12/3/2008 | 12/3/2008 9:48:26 AM | A | PASS |
|
|
24 hour air test passed
|
BLD08-00575
| FIRE-Final Inspection | 12/2/2008 | 12/3/2008 | 12/2/2008 2:53:00 PM | A | PASS |
|
|
Life safety passed. The fire hydrant at the property entrance that is mounted too high will be followed up on by the fire dept. Mark Sentenno is aware of the problem.
|