Inspections for the day of: Friday, December 3, 2010.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00128 FIR-Aging Inspection12/3/201012/3/201012/8/2010 2:18:26 PM PASS
Permit final okay- work completed.
BLD10-01868 BLD-Aging Inspection12/3/201012/3/201012/7/2010 5:08:42 PMAFAIL
Site visit confirmed correction items are not complete. Phoned Todd the tenant manager at ####-#### and left message regarding conditions for certificate of occupancy.
FIR10-00565 INSP-Final Inspection12/2/201012/3/201012/6/2010 5:14:56 PMANR
FIR10-00470 INSP-Sprinkler Rough-in12/2/201012/3/201012/3/2010 2:42:10 PMPFAIL
Overhead hydrostatic test failed due to 7 psi pressure loss at the guage. Manifold and FDC hydro test passed.
FIR10-00257 INSP-Conference12/3/201012/3/201012/3/2010 2:03:21 PMPDONE
Regarding project schedule.
BLD10-02610 FIRE-Final Inspection12/2/201012/3/201012/3/2010 12:59:00 PMAPASS
Tenant to provide approved door hardware at the second exit and repair one EM light at the main entry prior to structural final as discussed.
BLD10-01201 FIRE-Conference12/3/201012/3/201012/3/2010 12:56:52 PMADONE
Regarding project related fire alarm work.
BLD10-01637 FIRE-Conference12/3/201012/3/201012/3/2010 11:49:09 AMADONE
Regarding fire alarm notification at the restroom remodel.
BLD10-02103 FIRE-Final Inspection11/30/201012/3/201012/3/2010 11:17:07 AMAFAIL
Correction items include provide approved hardware at the main entry/exit door, remove manual surface and thumbturn locks at the west basement exit door, repair exit sign/EM light at the basement, doors/ hardware and ramp at the east exit are not yet installed or finished.