FIR06-00254
| INSP-Conference | 11/24/2010 | 12/1/2010 | | A | |
|
|
Follow up inspection. Steve Bevans ###-####
|
FIR10-00052
| FIR-Aging Inspection | 12/3/2010 | 12/3/2010 | 12/7/2010 2:47:09 PM | | PASS |
|
|
|
FIR10-00321
| FIR-Aging Inspection | 12/3/2010 | 12/3/2010 | 12/7/2010 2:22:07 PM | | PASS |
|
|
|
FIR10-00509
| INSP-Sprinkler Rough-in | 12/3/2010 | 12/3/2010 | 12/6/2010 9:49:41 AM | P | CANC |
|
|
Was canceled due to time constraints.
|
BLD10-00114
| FIRE-Final Inspection | 12/3/2010 | 12/3/2010 | 12/3/2010 1:06:01 PM | P | CANC |
|
|
The life safety inspection was unable to happen today due to the project related fire alarm and fire sprinkler permits still being unable to pass final inspection when I was at the job site at 8:30 this morning. When I arrived for a second visit at 11:15 I met building inspector Jim Sly. We met with John the architect and went over the outstanding fire alarm and fire sprinkler items and some of the obvious life safety items such as missing panic hardware, exit light at the main door and the wheelchair lift for the stage. John is going to try to have everything wrapped up for a re-inspection for monday morning.
|
FIR10-00406
| INSP-Alarm Testing | 12/2/2010 | 12/3/2010 | 12/3/2010 1:00:36 PM | A | FAIL |
|
|
I found several overspaced visual devices. I also noted that a room shown on the plans as Prayer is now a mens restroom. The a/v in this room appears to provide adequate coverage. With todays schedule I did not have the extra time to waite at the job site while Items were corrected. No testing was performed. Inspection to be rescheduled.
|
FIR10-00072
| INSP-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 12:55:03 PM | A | FAIL |
|
|
Need to perform a job walk through and verify there are no head obstructions, need all of the final items at the riser such as backflow certification, head box, stickers...ect. Also noted that a pendant head was installed in the electrical room but a ceiling had not been installed.
|
BLD10-02523
| FIRE-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 11:32:54 AM | P | PASS |
|
|
Life safety passed
|
BLD10-02534
| FIRE-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 11:32:19 AM | P | PASS |
|
|
Life safety passed.
|
FIR10-00611
| INSP-Final Inspection | 12/3/2010 | 12/3/2010 | 12/3/2010 11:08:52 AM | P | CANC |
|
|
Troy, Please call me as soon as you know an approximate time. Thank you! Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
|
BLD09-00667
| FIRE-Conference | 12/2/2010 | 12/3/2010 | 12/3/2010 10:56:13 AM | A | PASS |
|
|
life safety passed
|
FIR10-00572
| INSP-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 10:55:31 AM | P | PASS |
|
|
Permit finaled
|
FIR10-00573
| INSP-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 10:55:06 AM | P | PASS |
|
|
Permit finaled.
|
FIR10-00072
| INSP-Supply line flush | 12/2/2010 | 12/3/2010 | 12/3/2010 10:52:21 AM | A | PASS |
|
|
supply line flush passed.
|
FIR10-00072
| INSP-Sprinkler Rough-in | 12/2/2010 | 12/3/2010 | 12/3/2010 10:51:33 AM | A | PASS |
|
|
The underground flush passed and the forward flush test of the backflow preventor passed.
|
BLD10-02695
| FIRE-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 10:08:29 AM | A | CANC |
|
|
Provide fire extinguisher mounted in a normally occupied area with a current inspection tag. The suite number being a letter is ok per addressing.
|
BLD10-02168
| FIRE-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 10:04:13 AM | A | PART |
|
|
The new south end is ok to occupy. The new door magnets are to remain inoperative until the fire alarm contractor submits on this work and the devices are tested.
|
FIR10-00480
| INSP-Final Inspection | 12/1/2010 | 12/3/2010 | 12/3/2010 10:01:30 AM | A | FAIL |
|
|
The duct smoke detectors tested ok but door magnets have been added to the front and rear doors. This work shall be submitted. They wee not tested.
|