Inspections for the day of: Friday, December 3, 2010.
Number of inspections: 18
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00254 INSP-Conference11/24/201012/1/2010 A 
Follow up inspection. Steve Bevans ###-####
FIR10-00052 FIR-Aging Inspection12/3/201012/3/201012/7/2010 2:47:09 PM PASS
FIR10-00321 FIR-Aging Inspection12/3/201012/3/201012/7/2010 2:22:07 PM PASS
FIR10-00509 INSP-Sprinkler Rough-in12/3/201012/3/201012/6/2010 9:49:41 AMPCANC
Was canceled due to time constraints.
BLD10-00114 FIRE-Final Inspection12/3/201012/3/201012/3/2010 1:06:01 PMPCANC
The life safety inspection was unable to happen today due to the project related fire alarm and fire sprinkler permits still being unable to pass final inspection when I was at the job site at 8:30 this morning. When I arrived for a second visit at 11:15 I met building inspector Jim Sly. We met with John the architect and went over the outstanding fire alarm and fire sprinkler items and some of the obvious life safety items such as missing panic hardware, exit light at the main door and the wheelchair lift for the stage. John is going to try to have everything wrapped up for a re-inspection for monday morning.
FIR10-00406 INSP-Alarm Testing12/2/201012/3/201012/3/2010 1:00:36 PMAFAIL
I found several overspaced visual devices. I also noted that a room shown on the plans as Prayer is now a mens restroom. The a/v in this room appears to provide adequate coverage. With todays schedule I did not have the extra time to waite at the job site while Items were corrected. No testing was performed. Inspection to be rescheduled.
FIR10-00072 INSP-Final Inspection12/2/201012/3/201012/3/2010 12:55:03 PMAFAIL
Need to perform a job walk through and verify there are no head obstructions, need all of the final items at the riser such as backflow certification, head box, stickers...ect. Also noted that a pendant head was installed in the electrical room but a ceiling had not been installed.
BLD10-02523 FIRE-Final Inspection12/2/201012/3/201012/3/2010 11:32:54 AMPPASS
Life safety passed
BLD10-02534 FIRE-Final Inspection12/2/201012/3/201012/3/2010 11:32:19 AMPPASS
Life safety passed.
FIR10-00611 INSP-Final Inspection12/3/201012/3/201012/3/2010 11:08:52 AMPCANC
Troy, Please call me as soon as you know an approximate time. Thank you! Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
BLD09-00667 FIRE-Conference12/2/201012/3/201012/3/2010 10:56:13 AMAPASS
life safety passed
FIR10-00572 INSP-Final Inspection12/2/201012/3/201012/3/2010 10:55:31 AMPPASS
Permit finaled
FIR10-00573 INSP-Final Inspection12/2/201012/3/201012/3/2010 10:55:06 AMPPASS
Permit finaled.
FIR10-00072 INSP-Supply line flush12/2/201012/3/201012/3/2010 10:52:21 AMAPASS
supply line flush passed.
FIR10-00072 INSP-Sprinkler Rough-in12/2/201012/3/201012/3/2010 10:51:33 AMAPASS
The underground flush passed and the forward flush test of the backflow preventor passed.
BLD10-02695 FIRE-Final Inspection12/2/201012/3/201012/3/2010 10:08:29 AMACANC
Provide fire extinguisher mounted in a normally occupied area with a current inspection tag. The suite number being a letter is ok per addressing.
BLD10-02168 FIRE-Final Inspection12/2/201012/3/201012/3/2010 10:04:13 AMAPART
The new south end is ok to occupy. The new door magnets are to remain inoperative until the fire alarm contractor submits on this work and the devices are tested.
FIR10-00480 INSP-Final Inspection12/1/201012/3/201012/3/2010 10:01:30 AMAFAIL
The duct smoke detectors tested ok but door magnets have been added to the front and rear doors. This work shall be submitted. They wee not tested.