FIR13-00504
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/18/2013 4:58:59 PM | P | PART |
|
|
|
FIR13-00509
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/18/2013 4:58:25 PM | P | PART |
|
|
|
FIR13-00638
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/4/2013 7:13:37 AM | P | PART |
|
|
Overhead rough-in inspection completed- Refer to dated annotations on plans for areas in need of revision. Add missing head at the stock area SW corner, maintain coverage at the janitors room, pendents in the mens RR are at min. separation, provide coverage for the cart corral below the CCTV room, front entry vestibule and canopy are not yet constructed. Spacing adjustments at the NE wall okayed. Area separation walls to be full height in the stock room offices as discussed.
|
FIR13-00628
| INSP-Sprinkler Rough-in | 12/3/2013 | 12/3/2013 | 12/4/2013 7:05:38 AM | P | PART |
|
|
Refer to plans for dated annotations. Overhead work okayed to cover with the exception of three heads to be relocated due to spacing issues, and two hangers at armovers. Also clouded one area at the north side area "A" not ready for cover approval.
|
BLD13-01637
| FIRE-Final Inspection | 12/2/2013 | 12/3/2013 | 12/3/2013 11:25:51 AM | A | DEFR |
|
|
Diane Phone #: ###-#### * Incorrect permit number request- There are no FIR inspections related to this project. Phoned listed contact to inform
|
FIR13-00608
| INSP-Sprinkler Rough-in | 12/3/2013 | 12/3/2013 | 12/3/2013 11:12:16 AM | A | PART |
|
|
Overhead fire sprinkler work at the grid ceilings approved for cover. Ref. dated annotations on plans.
|
FIR13-00440
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/3/2013 11:09:44 AM | A | NR |
|
|
Project not in condition to complete a satisfactory pump acceptance test at this time.
|