BLD13-02849
| FIRE-Final Inspection | 12/3/2013 | 12/3/2013 | 12/3/2013 3:24:18 PM | P | FAIL |
|
|
Fire extinguishers are expired. I also noted an additional office has been built that is not shown on the plans.
|
FIR13-00535
| INSP-Final Inspection | 12/2/2013 | 12/3/2013 | 12/3/2013 2:09:11 PM | A | FAIL |
|
|
Two of the four fire/smoke dampers did not operate. Also need as-builts submitted.
|
FIR13-00674
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/3/2013 11:44:24 AM | A | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD13-02772
| FIRE-Final Inspection | 12/2/2013 | 12/3/2013 | 12/3/2013 11:43:50 AM | A | PASS |
|
|
Life safety passed
|
FIR13-00193
| INSP-Sprinkler Rough-in | 12/2/2013 | 12/3/2013 | 12/3/2013 11:37:33 AM | A | PART |
|
|
Sprinkler piping is ok to cover. Plans need to be resubmitted addressing the pipe size that does not match the approved plans.
|
BLD13-03297
| FIRE-Final Inspection | 12/3/2013 | 12/3/2013 | 12/3/2013 11:34:05 AM | P | PART |
|
|
A temp. occupancy was given until: Repair the bulb on the emergency light, remove the deadbolt from the east exit, provide keyed hardware on the inside deadbolt of the south exit.
|
BLD13-03313
| FIRE-Final Inspection | 12/2/2013 | 12/3/2013 | 12/3/2013 10:56:40 AM | A | FAIL |
|
|
Repair the exit sign and emergency light as marked on the plans. I noted that the fire rated door appears to have problems and suggested a conference with the building inspection.
|