Inspections for the day of: Wednesday, December 3, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03272 Conference12/3/201412/3/201412/3/2014 2:16:15 PMPDONE
Berry Phone #: ###-#### Discussed bonding of grounded conductor at central terminaton box and equipment grounding off grounded conductor at main disconnects.
ELE14-03328 Permanent Service12/3/201412/3/201412/3/2014 1:45:05 PMPFAIL
This Is A Request For Permanent Service The House has been vacant for Over A Year. We Did A Walkthrough Yesterday And there Are Some issues For Sure. Please call Gerald With a 30 Minute Advance Notice To Get The House Opened Please Call Gerald @###-#### Thanks And Have the Best Day Ever! Phone #: ###-#### Inspection requested via web by jason shifflett 200.2- Grounding conductor unsed as grounded conductor at sub panel in closet off kitchen shall be insulated.
210.63- A lighting outlet and service receptical is required for heating equiptment located in crawl space.
250.53(D)(2)- Where metal water pipe is used as a grounding electrode system it shall be supplemented by additional rods.
300.3- Hot tub circuit shall be ran in a conduit or cable assembly. Remove or replace.
ELE14-03152 Final12/2/201412/3/201412/3/2014 12:36:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
ELE14-02668 Final12/3/201412/3/201412/3/2014 11:32:22 AMPPASS
install 1 pole sign onto existing sign. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE14-02535 Final12/2/201412/3/201412/3/2014 10:52:48 AMANH
Contact: Shane Korte Phone #: ###-#### Inspection requested via web by Deb Gooden Unable to locate area of work. No answer from contact and no return call.
ELE14-02787 Final12/3/201412/3/201412/3/2014 10:21:13 AMAPASS
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE14-02788 Final12/3/201412/3/201412/3/2014 10:11:11 AMAPASS
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE14-03132 Electrical Rough-In12/2/201412/3/201412/3/2014 8:34:27 AMAPASS
Please inspect final underground pipe work at exterior pad site. Phone #: ###-#### Inspection requested via web by ERIC CENTERS Rough in ok cover