Inspections for the day of: Wednesday, December 3, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03327 Temporary Service12/3/201412/3/201412/3/2014 12:54:51 PMPDONE
Tim is the General Contractor and will be available by phone. Phone #: ###-#### Inspection requested via web by John Harvey
TS, OH, N, OK
ELE14-03285 Permanent Service11/26/201412/3/201412/3/2014 12:32:58 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder
PS, OH, N, OK
ELE13-02557 Electrical Rough-In12/3/201412/3/201412/3/2014 11:58:41 AMPDONE
Dave-customer not sure what type of inspection it is-please call prior homeowner would like to talk to you Phone #: ###-####
Conference for next step on what to do. Discussed arc fault requirements, and 4 wire requirements for range and dryer since existing panel is now sub panel. OK to cover final wall
ELE14-03325 Temporary Service12/3/201412/3/201412/3/2014 11:14:59 AMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
TS,UG,N,OK
ELE14-03329 Electrical Rough-In12/3/201412/3/201412/3/2014 11:12:52 AMPCANC
Floor heat master bathroom Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Inspection cancelled from web by: Chris Chesnut
ELE13-00238 ELE-Aging Inspection12/3/201412/3/201412/3/2014 10:55:16 AM DONE
left message for Kevin
ELE14-03299 Electrical Rough-In12/3/201412/3/201412/3/2014 10:43:05 AMPPASS
call Joe Levitch (###-####) for access, 1/2 hr heads up would be great - Thanks Phone #: ###-#### Inspection requested via web by Andy Derrick
Master bath floor heat, OK to cover
ELE14-03299 Electrical Rough-In12/3/201412/3/201412/3/2014 10:40:23 AMAPASS
Floor heat, master bath OK to cover
ELE14-03299 Electrical Rough-In12/2/201412/3/201412/3/2014 10:07:04 AMANH
contact - Joe Levitch ###-#### Phone #: ###-#### Inspection requested via web by Andy Derrick
third trip here, no access
ELE14-03298 Electrical Rough-In12/2/201412/3/201412/3/2014 9:44:56 AMAPASS
Phone #: ###-#### Inspection requested via web by kendall bender
RI ok to cover
ELE14-02616 Final12/2/201412/3/201412/3/2014 9:08:26 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jay Symonds
talked to contractor
210.8A2 GFI protection required garage
210.8A7 GFI protection required within 6 foot of sink
422.31A permanently installed appliance requires disconnecting means
ELE14-03299 Final12/2/201412/3/201412/2/2014 4:29:42 PMAFAIL
Floor heat to be installed to product specs and listings.