Inspections for the day of: Wednesday, December 3, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00747 INSP-Final Inspection12/2/201412/3/201412/3/2014 3:21:00 PMAPASS
Permit finaled
FIR14-00853 INSP-Sprinkler Rough-in12/2/201412/3/201412/3/2014 3:09:05 PMAPASS
See the city approved plans for pendant head locations where piping is ok to cover.
FIR14-00544 INSP-Final Inspection12/2/201412/3/201412/3/2014 2:59:18 PMAPASS
Permit finaled
BLD14-00206 FIRE-Final Inspection12/2/201412/3/201412/3/2014 2:31:59 PMAPASS
Life safety. Apartment numbers to be installed prior to a building inspection
BLD14-02721 FIRE-Final Inspection12/2/201412/3/201412/3/2014 2:31:23 PMAPASS
life safety passed
FIR14-00279 INSP-Alarm Testing12/3/201412/3/201412/3/2014 12:47:22 PMADONE
Finished except for the supervisory signals, low air and tamper, from the pre-action system.
FIR14-00861 INSP-Sprinkler Rough-in12/2/201412/3/201412/3/2014 12:03:05 PMAPASS
Underground supply piping is ok to cover.
BLD14-02333 FIRE-Final Inspection12/2/201412/3/201412/3/2014 9:50:25 AMAPASS
life safety passed
FIR14-00454 INSP-Final Inspection12/2/201412/3/201412/3/2014 9:31:18 AMAFAIL
Missing canopies and shipping clips are still on some of the pendant heads
FIR14-00544 INSP-Final Inspection12/2/201412/3/201412/3/2014 9:05:25 AMAPASS
Permit finaled