Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC14-05180 Rough-in12/3/201412/3/201412/3/2014 12:00:00 AMPFAIL
The chase built to continue to the first floor is required to be built as a rated shaft design per the mechanical plans.
The return air at the basement cannot terminate as above ceiling and create a plenum. Must be ducted to the kitchen area. Called the mechanical engineer and informed him of these issues that are going to need to be addressed.