BLD15-03854
| FIRE-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 2:07:01 PM | P | PART |
|
|
There are two existing fire sprinklers located (Appears that there use to be a drop ceiling in this location) in the entry of the tenant space. Upright protection in the entry way is sufficient, no need for the extra two fire sprinkler heads. Contractor will have the heads removed and plugged. All other items for life fire safety inspection passed/complete.
|
BLD15-03784
| FIRE-Final Inspection | 12/3/2015 | 12/3/2015 | 12/3/2015 1:52:01 PM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete. Life fire safety passed/complete
|
BLD15-02802
| FIRE-Final Inspection | 12/3/2015 | 12/3/2015 | 12/3/2015 1:37:04 PM | P | PASS |
|
|
No fire alarm modifications, fire sprinkler inspection complete. Life fire safety inspection passed/complete.
|
BLD15-03404
| FIRE-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 11:26:05 AM | A | PASS |
|
|
No fire sprinkler modifications, fire alarm inspection complete. Life fire safety inspection passed/complete.
|
BLD15-02835
| FIRE-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 10:30:07 AM | A | FAIL |
|
|
Door hardware on all doors is of the round knob type, door hardware needs to be changed to single action type door handles. Thumb-turn deadbolt located on west side exit door needs to be removed. Signage reading "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED” needs to be installed on front main entry, tenant is allowed one double keyed deadbolt, currently two deadbolts are installed on front main entry (East side entry). Maximum occupancy sign needs to be installed. City approved plans and small documentation not readily avaiable at time of inspection.
|
BLD15-01965
| FIRE-Final Inspection | 12/3/2015 | 12/3/2015 | 12/3/2015 9:57:13 AM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete. Life fire safety passed/complete.
|
FIR15-00603
| INSP-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 9:52:16 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00624
| INSP-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 9:51:19 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|