ELE97-03837
| INSP - Electrical Rough-In | 12/29/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | A | PART |
|
|
12/29/98 403 - Doug ###-#### pager REQUESTED CONFERENCE ONLY, DISCUSSED SERVICE EQUIPTMENT CLEARENCES IN EQ
|
ELE98-01230
| INSP - Final | 12/29/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | A | FAIL |
|
|
12/29/98 403 - CODY ###-#### NEC: 250-91(A)(C). GROUNDING ELECTRODE REQUIRED FOR STREET LIGHTS. ALSO, REINSPECTION FEE REQUIRED,(3RD INSPECTION).
|
ELE98-04097
| INSP - Final | 12/29/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | A | PASS |
|
|
12/29/98 403 - BRANDON ###-#### OK
|
ELE98-04440
| INSP - Electrical Rough-In | 12/29/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | A | PART |
|
|
DAWN ###-#### PERM/SVC FOR CONNECTION OF SERVICE ENTRANCE CONDUCTORS ONLY. STILL NEED CONCRETE ENCASED GROUNDING CONDUCTOR; ELE R/I OF INTERIOR ADDITION OK.
|
ELE98-04519
| INSP - Final | 12/30/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | P | FAIL |
|
|
12/30/98 403 - marcie ###-#### fn insp ..trans jms.. NEC: 373-4. OPENINGS SHALL BE CLOSED. NEC: 250-83(C)(3). GROUNDING ELECTRODE SHALL BE FLUSH. LEFT MESSAGE ON ANSWERING MACHINE, CONTACTED CONTRACTOR.
|
ELE98-02389
| INSP - Final | 12/30/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | P | PASS |
|
|
12/30/98 403 - DAVID ###-#### WILL NOT BE HOME UNTIL 2:00 DETACHED ART-STUDIO. OK
|
ELE98-03195
| INSP - Electrical Rough-In | 12/29/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | P | PART |
|
|
12/30/98 403 - ED ###-#### GROUND-WORK PVC CONDUIT; TREATMENT PLANT.
|
ELE98-03695
| INSP - Final | 12/30/1998 | 12/30/1998 | 12/30/1998 12:00:00 AM | P | PASS |
|
|
12/30/98 403 - JOHN ###-#### OK
|