FIR02-00142 FIR-Aging Inspection12/30/200212/30/200212/30/2002 12:00:00 AM NR
called Simplex and talked to Chris and he said he would look into and thought that it had been tested already 12/30/2002 1:24:41 PM
BLD00-03428 FIRE-Conference12/30/200212/30/200212/30/2002 12:00:00 AMAPART
met with Steve of LEA Electirc; c/n issued - need detectors installed within 5 ft of smoke/fire dampers; need access doors at all dampers; will need to verify duct detector operation with air differential pressure test per Simplex manual instructions; duct detectors are installed at some smoke/fire dampers - plans show in-duct detectors; numerous pockets in computer room ceiling which will require detectors for pre-action system 12/30/2002 11:00:34 AM
FIR02-00411 INSP-Conference12/30/200212/30/200212/30/2002 12:00:00 AMAPART
met with Steve of LEA Electirc; c/n issued - need detectors installed within 5 ft of smoke/fire dampers; need access doors at all dampers; will need to verify duct detector operation with air differential pressure test per Simplex manual instructions; duct detectors are installed at some smoke/fire dampers - plans show in-duct detectors; numerous pockets in computer room ceiling which will require detectors for pre-action system 12/30/2002 11:00:43 AM
BLD02-02445 FIRE-Final Inspection12/30/200212/30/200212/30/2002 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
FIR02-00472 INSP-Final Inspection12/30/200212/30/200212/30/2002 12:00:00 AMPPASS
BLD02-02065 FIRE-Final Inspection12/30/200212/30/200212/30/2002 12:00:00 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung 12-30-02 ROB CANC THIS INSPECTION NOT READY