Inspections for the day of: Monday, December 30, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00258 FIR-Aging Inspection12/30/200212/30/200212/30/2002 12:00:00 AM NR
work in progress 12/30/2002 12:47:48 PM
BLD01-00357 FIRE-Final Inspection12/27/200212/30/200212/30/2002 12:00:00 AMAFAIL
gary ###-#### I could not contact the contractor with the phone number listed. I stopped at the job site and no one could provide drawings. I was given an office number for the contractor and left a message there 12/30/2002 11:40:00 AM
BLD01-03230 FIRE-Final Inspection12/23/200212/30/200212/30/2002 12:00:00 AMPFAIL
###-#### STEVE The fire door for the 2nd floor freight elevator does not latch when the fire alarm system is activated, provide a/v's within 15' of the ends of the corridors on the first and second floors, provide verification of fire/smoke damper activation per review comment #6, revise zone description and the FACP text so they match the device test and then retest, verify signals with the monitoring company, verify with the inspector the current draw on the notification circuits, provide map per review note #7, test the initiating devices. No area or duct smoke detectors were tested due to zone descriptions not matching. Do not final permit until the owner has the approved building plans on site 12/30/2002 4:23:28 PM