ELE04-04067 Permanent Service12/28/200412/30/200412/30/2004 12:00:00 AMAPASS
100 amp service upgrade, circuit to microwave, circuit to outlets in soffit. Internet Inspection Request from: Andy Rose told owner they had to move shelves for clearance. ok to final 12/30/2004 8:18:58 AM
ELE04-04100 Rough-In Permanent Service12/29/200412/30/200412/30/2004 12:00:00 AMAPASS
###-#### allan ok to cover p/s u/g n ok 12/30/2004 10:10:28 AM
ELE04-04101 Rough-In Permanent Service12/29/200412/30/200412/30/2004 12:00:00 AMAPASS
###-#### allan ok to cover p/s u/g n ok 12/30/2004 10:11:34 AM
ELE04-02500 Final12/29/200412/30/200412/30/2004 12:00:00 AMAFAIL
Terry-call 1/2 hr ahead; Phone #: ###-#### Internet Inspection Request from: Jan Rice 314.17(A) pump diaconnect shall have ko seals installed,250.94 provide ufer access, 250.104(A) bond to metal water piping shall be provided, , 250.110 ground wire in service shall be attached, 110.27(A) dead-front shall be provided in service, 200.11 recepts shall be correct polarity in kitchen, master bath, and jetted tub area. 12/30/2004 9:45:32 AM
ELE04-04017 Electrical Rough-In12/30/200412/30/200412/30/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/30/2004 at 8:29:16 AM. Contact: ###-####. 250.86 raceway shall be grounded thru concentric,358.30 emt shall be strapped within 3' of panel,110.26(F)(1)(b) leak protection shall be provided over panel, 210.62 showroom recpt shall be added 12/30/2004 1:07:53 PM
ELE04-04103 Final12/30/200412/30/200412/30/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final 12/30/2004 4:13:56 PM
ELE04-04074 Final12/30/200412/30/200412/30/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/30/2004 at 10:12:13 AM. Contact: ###-####. bcc states u/g inspection required before cover. called contr and also told to ask for p/s inspection when called back in. 12/30/2004 12:13:05 PM
ELE03-01543 Final12/30/200412/30/200412/30/2004 12:00:00 AMPPASS
john miller told owner to staple 2 romex over panel and finish panel schedule. Also told them to cover wiring above and below panel. ok to final 12/30/2004 2:57:58 PM