Inspections for the day of: Friday, December 30, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00526 INSP-Final Inspection12/30/200512/30/200512/30/2005 3:53:10 PMPPART
Contact Jeff at ###-#### Fire alarm functioned as required, devices in cleanroom to be verified for type and location at life safety final due to access issues, record of completion to be signed and permit finaled at that time.
FIR05-00848 INSP-Final Inspection12/29/200512/30/200512/30/2005 2:23:45 PMPFAIL
The two wall mounted strobes are below 80" AFF, need to provide an updated building map at the panel, not a complete inspection at this time.
FIR05-00471 INSP-Final Inspection12/30/200512/30/200512/30/2005 1:59:57 PMPPASS
Items needing correction have been completed, fire alarm passed inspection.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro12/29/200512/30/200512/30/2005 1:09:34 PMAPART
3rd and 4th level parking garage dry system 24 hr air test passed, discussed UG flush and testing schedule for next week.
BLD05-02270 FIRE-Final Inspection12/29/200512/30/200512/30/2005 12:16:20 PMAPASS
Fire life safety passed inspection, the provided fire extinguisher was installed while on site as discussed.
FIR05-00785 INSP-Final Inspection12/30/200512/30/200512/30/2005 12:14:52 PMPPASS
Fire alarm permit finaled.
FIR05-00774 INSP-Final Inspection12/30/200512/30/200512/30/2005 12:11:54 PMPPASS
Defficient items have been corrected, fire sprinkler permit finaled.
FIR05-00785 INSP-Alarm Testing12/28/200512/30/200512/30/2005 12:08:56 PMAPASS
Fire alarm passed inspection.
FIR05-00526 INSP-Final Inspection12/27/200512/30/200512/30/2005 10:58:01 AMACANC
Phone #: ###-#### Internet Inspection Request from: Dennis Holmes Inspection canceled per phone conversation with Andy Spirnock at ###-####, to be rescheduled at a later date.
FIR05-00615 INSP-Final Inspection12/27/200512/30/200512/30/2005 10:55:34 AMACANC
Andy Spirnock; Phone #: ###-#### Inspection canceled per phone conversation with Andy.
BLD05-03075 FIRE-Final Inspection12/29/200512/30/200512/30/2005 12:00:00 AMACANC
late am if possible please///jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore///cancelled per Jerry not ready will call later to reschedule, called Forrest 12/30/05 8:30am LEG