Inspections for the day of: Tuesday, December 30, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00626 INSP-Sprinkler Rough-in/Hydro12/30/200812/30/200812/30/2008 4:20:15 PMPPASS
The mens and womens locker rooms located along the north wall are ok to cover.
BLD07-03132 FIRE-Final Inspection12/29/200812/30/200812/30/2008 4:19:17 PMADONE
The new addition is passed the fire life safety inspection except the large pre-action computer room which still needs the hvac shut down and the alarm strobe repaired as noted on the project related fire alarm activities. Also the two rooms being remodeled in the existing portion of the facility need to be finished prior to a final on this project.
BLD08-01294 FIRE-Conference12/30/200812/30/200812/30/2008 4:16:31 PMPDONE
A fire alarm quick permit (FIR08-00732) was issued, inspected and passed for the addition of in-duct detectors at the vertical shaft between the 5th and 6th floors. It appears that the project related FIR08-00517 is still in the issued status.
FIR08-00732 INSP-Final Inspection12/29/200812/30/200812/30/2008 3:02:30 PMPPASS
permit finaled
FIR08-00369 INSP-Sprinkler Rough-in/Hydro12/29/200812/30/200812/30/2008 3:01:38 PMPCANC
To be rescheduled
FIR08-00341 INSP-Alarm Testing12/24/200812/30/200812/30/2008 3:00:59 PMACANC
mark Phone #: ###-####
BLD08-02572 FIRE-Final Inspection12/30/200812/30/200812/30/2008 1:27:56 PMPPASS
Life safety passed. Building inspector to please verify that the max. height stickers are installed.
BLD08-02174 FIRE-Final Inspection12/29/200812/30/200812/30/2008 11:48:22 AMAFAIL
The exit signs and emergency lights have not been fixed yet.
BLD08-02571 FIRE-Final Inspection12/29/200812/30/200812/30/2008 11:25:08 AMAPASS
Life safety passed
BLD08-00640 FIRE-Final Inspection12/29/200812/30/200812/30/2008 10:04:43 AMAFAIL
There were no approved plans on site but I did a courtesy walk through. Fire extinguishers appear ok. Not all of the exit signs and emergency lights work. The smoke detectors for door release near the front lobby are closer than 3' to a supply register. The existing fire sprinkler riser inspection tag is expired. In the riser/storage room alot of wiring is attached to the sprinkler piping. Ceiling tile is missing is the sprinklered areas. No other items were looked due to missing plans.
FIR08-00605 INSP-Sprinkler Rough-in12/29/200812/30/200812/30/2008 9:25:50 AMAFAIL
Tony did not have the previous marked plans for review and there were alot of tenting issues and the piping in the pool has not been tented yet. No inspection was performed.
FIR07-00827 INSP-Sprinkler Rough-in12/29/200812/30/200812/30/2008 8:58:57 AMAPASS
Todays inspection was for a small area in the basement/lower level. See the city approved plans for pendant heads that are marked with "ok". These are ok for cover. There are some overspacing issues but per Don existing walls are coming down and coverage with be restored. I let him know that Forrest or I will need to verify. Also I circled some pockets behind columns where there is no sprinkler protection/floor coverage that will need to be addressed with protection or an exception in the code.